508107-01
Issue 2041
Page 15 of 58
Figure 8.
Primary Limit Location and Heat Exchanger
Flame Signal In Microamps
Normal
Low
Drop Out
1.5
0.5 - 1.4
0.4
Set Dial to DC MicroAmps
(+)
Multi−Meter
(+)
(+) To Control
Sensor Terminal
(−) To Flame
Terminal
Flame Sensor
Terminal
Flame Sensor
Wire
Intergrated
Control
Remove sensor from integrated
control and connect alligator clip
(−) to flame sensor lead.
Remove sensor from integrated
control and connect alligator clip
(+) to terminal on control.