background image

508187-01

Issue 2116

Page 23 of 51

Heating Components

Ignitor

The ignitor is made of durable silicon nitride. The integrated 

control  provides  120  volts  to  the  ignitor  for  a  consistent 

ignition and long ignitor life. Ohm value should be 39 to 70. 

See Figure 9 for ignitor location and Figure 10 for ignitor 

check out.

NOTE: 

The A80UH2E / 80G2UHE(L) furnace contains 

electronic components that are polarity sensitive. Make 

sure that the furnace is wired correctly and is properly 

grounded.

Flame Sensor

A  flame  sensor  is  located  on  the  left  side  of  the  burner 

support. See Figure 9. The sensor tip protrudes into the 

flame  envelope  of  the  left-most  burner.  The  sensor  can 

be removed for service without removing any part of the 

burners.  During  operation,  flame  is  sensed  by  current 

passed  through  the  flame  and  sensing  electrode.  The 

control  allows  the  gas  valve  to  remain  open  as  long  as 

flame signal is sensed. To check flame sense signal use 

the push-button found on the integrated control and go to 

Field Test Mode. The menu will display the flame signal. 

See Table 8 for flame signal.

To Measure Flame Signal - Integrated Control:

Use  a  digital  readout  meter  capable  of  reading  DC 

microamps.  See  Figure  11  and  Table  8  for  flame  signal 

check.

1. 

Set the meter to the DC amps scale.

2.  Turn off supply voltage to control.

3. 

Disconnect integrated control flame sensor wire from 

the flame sensor.

4. 

Connect (-) lead to flame sensor.

5. 

Connect (+) lead to the ignition control sensor wire.

6. 

Turn supply voltage on and close thermostat contacts 

to cycle system.

7. 

When main burners are in operation for two minutes, 

take reading.

Normal

Low

Drop Out

2.6 or greater

2.5 or less

0.06

Table 8. Flame Signal in Microamps

Gas Valve

The  valve  (Figure  14)  is  internally  redundant  to  assure 

safety shut-off. If the gas valve must be replaced, the same 

type valve must be used.

24VAC terminals and gas control knob are located on the 

valve. A wire harness connects the terminals from the gas 

valve to the electronic ignition control. 24V applied to the 

terminals energizes the valve.

Inlet and outlet pressure taps are located on the valve. A 

regulator adjustment screw is located on the valve.

LPG change over kits are available from Allied. Kits include 

burner orifices and a gas valve.

Flame Rollout Switches (S47)

Flame rollout switch is a high temperature limit located on 

top of the burner box, one on each side.- See Figure 9. 

The  limit  is  a  N.C.  SPST  manual-reset  limit.  When  S47 

senses rollout, the circuit breaks and the ignition control 

immediately  stops  ignition  and  closes  the  gas  valve. 

Rollout can be caused by a blocked exchanger, flue or lack 

of combustion air. The switch is factory set to trip (open) at 

210°F and cannot be adjusted. The switch can be manually 

reset. To manually reset a tripped switch, push the reset 

button located on the control.

Burners

All units use inshot burners. Burners are factory set and 

require  no  adjustment. Always  operate  the  unit  with  the 

burner box front panel in place. Each burner uses an orifice 

that is precisely matched to the burner input. Burners can 

be removed as a one piece assembly for service. If burner 

assembly has been removed, it is critical to align center 

of  each  burner  to  the  center  of  the  clamshell  when  re-

installing. See more detail in the Maintenance section.

Primary Limit Control (S10)

The primary limit (S10) is located in the heating vestibule 

panel. When excess heat is sensed in the heat exchanger, 

the limit will open. If the limit is open, the furnace control 

energizes the supply air blower and closes the gas valve. 

The  limit  automatically  resets  when  unit  temperature 

returns  to  normal.  The  switch  must  reset  within  three 

minutes  or  the  control  will  go  into  Watch  guard  for  one 

hour. The switch is factory set and cannot be adjusted. The 

switch may have a different set point for each unit model 

number. 

Содержание 80G2UHE

Страница 1: ...e this symbol on labels or in manuals be alert to the potential for personal injury or death Electric shock hazard Can cause injury or death Before attempting to perform any service or maintenance turn the electrical power to unit OFF at disconnect switch es Unit may have multiple power supplies WARNING As with any mechanical equipment contact with sharp sheet metal edges can result in personal in...

Страница 2: ...H2E090B16 88 000 69 000 57 000 46 000 80 0 4 1 2 120 60 1 15 8 2 40 3 4 140 A80UH2E110C16 110 000 86 000 72 000 58 000 80 0 4 1 2 120 60 1 15 8 2 40 3 4 152 A80UH2E110C20 110 000 87 000 72 000 58 000 80 0 5 1 2 120 60 1 15 10 0 40 1 156 Note For vent length and clearances to combustibles please reference installation instructions Note Filters and provisions for mounting are not furnished and must ...

Страница 3: ...fm Watts 0 00 1375 340 1350 240 1110 190 970 93 780 50 0 10 1350 346 1325 254 1100 194 940 104 725 57 0 20 1330 346 1310 264 1080 200 895 113 680 64 0 30 1315 353 1280 272 1060 204 860 118 610 70 0 40 1300 368 1250 283 1040 212 810 125 550 76 0 50 1285 369 1220 293 1010 222 765 132 510 78 0 60 1260 384 1190 301 975 227 725 140 460 83 0 70 1240 391 1150 314 950 236 680 147 400 89 0 80 1210 399 1120...

Страница 4: ...70 1050 239 905 193 0 70 1520 467 1255 344 1110 284 1000 249 840 202 0 80 1470 474 1215 352 1050 294 935 258 765 211 A80UH2E110C16 External Static Pressure in w g Air Volume Watts at Various Blower Speeds High Black Medium High Brown Medium Blue Medium Low Yellow Low Red cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts 0 00 1780 349 1570 248 1465 190 1370 169 1250 131 0 10 1750 365 1540 260 1420 ...

Страница 5: ...0 00 2175 590 2050 410 1850 310 1695 275 1510 195 2175 605 1930 420 1785 320 1675 260 1500 195 0 10 2158 607 1943 421 1778 328 1650 283 1461 205 2129 628 1892 441 1733 345 1627 288 1458 209 0 20 2131 620 1897 436 1719 345 1591 299 1405 215 2091 649 1838 458 1691 360 1586 297 1407 220 0 30 2085 639 1847 456 1678 354 1563 308 1351 228 2072 660 1806 471 1631 371 1529 313 1353 232 0 40 2055 652 1806 4...

Страница 6: ...01 2 Stage 80 UH DF Propane Gas 11K47 Natural to LP Kits 2 Stage 80 UH DF 0 7500 ft 11K48 2 Stage 80 UH DF 7501 10 000 ft 11K47 LP to Natural Kits 2 Stage 80 UH DF 77W10 Downflow Specific Air Filters 14 5 51W06 17 5 51W07 Downflow Combustible Flooring Base 14 5 11M59 17 5 11M60 Night Service Kits 2 Stage 22J94 Horizontal Suspension Kit 80 90 51W10 External Filter Rack Kits 1 pack 16 x 25 1 841018 ...

Страница 7: ...0 1 2 136 80G2UH090BE16 80G2UH090BE16L 88 000 69 000 57 000 46 000 80 0 4 1 2 120 60 1 15 8 2 40 3 4 140 80G2UH110CE16 110 000 86 000 72 000 58 000 80 0 4 1 2 120 60 1 15 8 2 40 3 4 152 80G2UH110CE20 80G2UH110CE20L 110 000 87 000 72 000 58 000 80 0 5 1 2 120 60 1 15 10 0 40 1 156 Note For vent length and clearances to combustibles please reference installation instructions Note Filters and provisi...

Страница 8: ...Watts cfm Watts 0 00 1605 313 1475 240 1320 173 1050 99 865 60 0 10 1565 323 1430 251 1270 185 995 108 800 68 0 20 1515 334 1380 264 1225 196 935 115 730 76 0 30 1475 347 1340 275 1170 207 870 124 645 83 0 40 1435 360 1300 285 1120 215 805 133 550 91 0 50 1395 369 1250 295 1065 225 715 140 470 98 0 60 1355 378 1205 307 1010 235 655 147 395 101 0 70 1305 391 1160 318 935 246 560 156 345 107 0 80 12...

Страница 9: ...2 1140 270 1050 239 905 193 0 70 1520 467 1255 344 1110 284 1000 249 840 202 0 80 1470 474 1215 352 1050 294 935 258 765 211 80G2UH110CE16 External Static Pressure in w g Air Volume Watts at Various Blower Speeds High Black Medium High Brown Medium Blue Medium Low Yellow Low Red cfm Watts cfm Watts cfm Watts cfm Watts cfm Watts 0 00 1780 349 1570 248 1465 190 1370 169 1250 131 0 10 1750 365 1540 2...

Страница 10: ...m Watts 0 00 2175 590 2050 410 1850 310 1695 275 1510 195 2175 605 1930 420 1785 320 1675 260 1500 195 0 10 2158 607 1943 421 1778 328 1650 283 1461 205 2129 628 1892 441 1733 345 1627 288 1458 209 0 20 2131 620 1897 436 1719 345 1591 299 1405 215 2091 649 1838 458 1691 360 1586 297 1407 220 0 30 2085 639 1847 456 1678 354 1563 308 1351 228 2072 660 1806 471 1631 371 1529 313 1353 232 0 40 2055 65...

Страница 11: ...W01 2 Stage 80 UH DF Propane Gas 11K47 Natural to LP Kits 2 Stage 80 UH DF 0 7500 ft 11K48 2 Stage 80 UH DF 7501 10 000 ft 11K47 LP to Natural Kits 2 Stage 80 UH DF 77W10 Downflow Specific Air Filters 14 5 51W06 17 5 51W07 Downflow Combustible Flooring Base 14 5 11M59 17 5 11M60 Night Service Kits 2 Stage 22J94 Horizontal Suspension Kit 80 90 51W10 External Filter Rack Kits 1 pack 16 x 25 1 841018...

Страница 12: ...ssure Switch Combustion Air Inducer Gas Valve and Manifold Assembly Limit Switch under collector box Collector Box Heat Exchanger Indoor Blower and Motor Assembly installed in cabinet Make Up Box Constant Torque Indoor Blower Motor removed from cabinet Two Stage Integrated Control ...

Страница 13: ... provides overcurrent protection to the transformer T1 The breaker is rated at 3A at 32V If the current exceeds this limit the breaker will trip and all unit operation will shutdown The breaker can be manually reset by pressing the button on the face See Figure 3 Figure 3 Circuit Breaker CB8 PRESS TO RESET Integrated Ignition Control A92 Shock hazard Disconnect power before servicing Control is no...

Страница 14: ...r purge and warm up time between trials of 35 seconds After a total of five trials for ignition including the initial trial the control goes into Watchguard Flame Failure mode After a 60 minute reset period the control will begin the ignition sequence again NOTE During abnormal conditions such as low supply voltage or low outdoor temperatures and the low fire pressure switch does not close the com...

Страница 15: ...UICK CONNECT TERMINALS NEUTRALS 120 VAC NEUTRAL HUM UNPOWERED NORMALLY OPEN DRY CONTACTS LI 120VAC INPUT TO CONTROL ACC 120VAC OUTPUT TO OPTIONAL ACCESSORY THERMOSTAT CONNECTIONS TB1 DS DEHUMIDIFICATION SIGNAL W2 HEAT DEMAND FROM 2ND STAGE TSTAT W1 HEAT DEMAND FROM 1ST STAGE TSTAT R CLASS 2 VOLTAGE TO TSTAT G MANUAL FAN FROM TSTAT C TSTAT SIGNAL GROUND CONNECTED TO TRANSFORMER GRD TR CHASSIS GROUN...

Страница 16: ...15 2 STAGE COMPR W951 HEAT PUMP W914 DEHUM CUT FOR OPTION SELECTION 1 2 3 4 5 6 ON W1W2 G Y2 Y1 C C DH L O DS R W1 W2 G Y2 Y1 C C R L DH 7 1 ON ON ON ON 90 SECOND HTG BLOWER OFF DELAY 1 2 3 4 5 6 7 ON 1 2 3 4 5 6 7 ON THERMOSTAT SELECTION 1 STAGE THERMOSTAT TIMED STAGING SEE SW 2 TWO STAGE THERMOSTAT 1 2 3 4 5 6 7 1 2 3 4 5 6 7 ON ON BLOWER ON DELAY 30 SEC FIXED 1 2 3 4 5 6 7 ON SENSE IGN CAI2 CAI...

Страница 17: ...ncy problems System resumes normal operation 5 seconds after fault recovered E115 Low 24V Control will restart if the error recovers 24 Volt Power Low Range is 18 to 30 volts Check and correct voltage Check for additional power robbing equipment connected to system May require installation of larger VA transformer to be installed in furnace air handler Clears after fault recovered E117 Poor ground...

Страница 18: ...sure good unit ground Alert clears after current heat call has been completed E241 Flame sensed out of sequence Flame still present Shut off gas Check for gas valve leak Replace if necessary Alert clears when fault is recovered E250 Limit switch circuit open Check for proper firing rate on furnace Ensure there is no blockage in heater Check for proper air flow If limit not closed within 3 minutes ...

Страница 19: ...splayed 10 minutes after entering the flame sense mode Integrated Control DIP Switches Integrated Control DIP Switches A80UH2E 80G2UHE L units are equipped with a two stage integrated control This control manages ignition timing heating mode fan off delays and indoor blower speeds based on selections made using the control dip switches and jumpers The control includes an internal watchguard featur...

Страница 20: ...gs Switches 6 and 7 Continuous Fan Mode Continuous fan speed can be controlled by changing DIP switch positions Table 7 provides DIP switch settings for continuous fan mode Continuous Fan Mode Switch 6 Switch 7 Low Heat Speed Factory Off Off Low Cool Speed Off On High Heat Speed On Off High Cool Speed On On Table 7 Continuous Fan Mode Settings Onboard Links W914 Dehum Onboard link W914 is a clippa...

Страница 21: ...e less than 20mA Troubleshooting the Motor Troubleshooting the motor is an easy process Follow steps below 1 Shut off power to unit 2 Remove input plugs P48 and P49 from motor See Figure 8 for troubleshooting procedure If correct voltage is present in tests 1 and 2 and motor is not operating properly replace motor The motor is not field repairable If replacing the indoor blower motor or blower whe...

Страница 22: ...t 3 Check for 120 volts across terminals L1 and Neutrals on the integrated control If voltage is present problem is with the harness If voltage is not present problem may be may be with the integrated control Switch thermostat to CONTINUOUS FAN MODE Check for 24 volts across terminal C on input plug P48 and speed tap used for continuous fan 1 2 3 4 or 5 on input plug P49 If 24 volts is not present...

Страница 23: ...e type valve must be used 24VAC terminals and gas control knob are located on the valve A wire harness connects the terminals from the gas valve to the electronic ignition control 24V applied to the terminals energizes the valve Inlet and outlet pressure taps are located on the valve A regulator adjustment screw is located on the valve LPG change over kits are available from Allied Kits include bu...

Страница 24: ...508187 01 Issue 2116 Page 24 of 51 Figure 9 Heating Components Gas Valve Gas Orifices Sensor Ignitor Burners Rollout Switches ...

Страница 25: ...e manifold and check resistance of the ignitor Reading should be betwenn 39 and 70 ohms If reading is correct then there is a problem with the wiring between the jack plug anf the control If reading is not correct the issue is the ignitor Meter set to ohms Test 3 Checking voltage to ignitor Insert meter probes into terminals 1 and 5 use small diameter probes in order to not damage plug Check volta...

Страница 26: ...L METER Red Collar Indicates Positive Leads To Control Sensor Terminal Flame Sensor Flame Sensor Wire Integrated Control Remove Sensor Wire from Integrated Control and Connect Alligator Clip to Frame Sensor Lead Flame Sensor Terminal Remove Sensor Wire from Integrated Control and Connect Alligator Clip to Terminal on Control ...

Страница 27: ...ure 12 A80UH2E 80G2UHE L series units are equipped with a dual combustion air pressure switch first and second stage located on the CEHB The switch is connected to the cold end header box by means of flexible silicone hoses It monitors negative differential pressure across the cold end header box orifice The switches are a single pole single throw pressure switches electrically connected to the in...

Страница 28: ...y consists of orifice plate proving switch gasket and combustion air inducer then reinstall the mounting screws See unit Installation Instructions for more detail The combustion air pressure switch must be moved for horizontal discharge air left position IMPORTANT Figure 13 FLOW AIR vent pipe FLOW AIR Vent Pipe FLOW AIR Vent Pipe Vent Pipe Vent Pipe vent pipe In all positions route the wires away ...

Страница 29: ...ccess panel 6 Move gas valve switch to OFF See Figure 14 7 Wait five minutes to clear out any gas If you then smell gas STOP Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you do not smell gas go to next step 8 Move gas valve switch to ON See Figure 14 Figure 14 Gas Valve GAS VALVE SHOWN IN ON POSITION INLET PRESSURE POST HIGH FIRE ADJUSTMENT S...

Страница 30: ...the gas supply line CAUTION Do not over torque 800 in lbs or under torque 350 in lbs when attaching the gas piping to the gas valve WARNING Testing Gas Piping In case emergency shutdown is required turn off the main shut off valve and disconnect the main power to unit These controls should be properly labeled by the installer IMPORTANT When pressure testing gas lines the gas valve must be disconne...

Страница 31: ...Flow Approximate Furnace should operate at least 5 minutes before checking gas flow Determine time in seconds for two revolutions of gas through the meter Two revolutions assures a more accurate time Divide by two and compare to time in Table 10 If manifold pressure matches Table 12 and rate is incorrect check gas orifices for proper size and restriction Remove temporary gas meter if installed NOT...

Страница 32: ...units 2 Natural gas high altitude orifice kit required 3 A natural to L P propane gas changeover kit is necessary to convert this unit Refer to the changeover kit installation instruction for the conversion procedure NOTE Units may be installed at altitudes up to 4500 ft above sea level without modifications Table 12 Manifold Pressure and Line Pressure at Various Altitudes Capacity High Altitude P...

Страница 33: ... of load indicates a poor or partial ground Compare the readings to Table 14 If the readings exceed the maximum shown in Table 14 make repairs before operating the furnace 2 In addition measure the AC voltage from Line Hot to Line Neutral spade terminals on the integrated control See Figure 16 This voltage should be in the range of 97 to 132 Vac Furnace Status Measurement VAC Expected Maximum Powe...

Страница 34: ...g plate Figure 17 TEMPERATURE RISE Supply Duct Temperature Return Duct Temperature _ Temperature Rise SUPPLY AIR Temperatures RETURN AIR External Static Pressure 1 Tap locations shown in Figure 18 2 Punch a 1 4 diameter hole in supply and return air plenums Insert manometer hose flush with inside edge of hole or insulation Seal around the hose with permagum Connect the zero end of the manometer to...

Страница 35: ... also cause the limit to trip more frequently during the winter and the indoor coil to freeze in the summer resulting in an increase in the number of service calls Before using any filter with this system check the specifications provided by the filter manufacturer IMPORTANT Cabinet Width Filter Size Side Return Bottom Return 14 1 2 16 x 25 x 1 14 x 25 x 1 17 1 2 16 x 25 x 1 21 20 x 25 x 1 Table 1...

Страница 36: ...ce inspection to ensure proper combustion and operation Consult Service Literature for proper combustion values 14 Verify operation of CO detectors and replace batteries as required Perform a general system test Turn on the furnace to check operating functions such as the start up and shut off operation 1 Check the operation of the ignition system inspect and clean flame sensor Check microamps bef...

Страница 37: ...am Begin from the burner opening on each clam Steam must not exceed 275 F 12 To clean burners run a vacuum cleaner with a soft brush attachment over the face of burners Visually inspect inside the burners and crossovers for any blockage caused by foreign matter Remove any blockage Figure 19 shows burner detail 13 To clean the combustion air inducer visually inspect and using a wire brush clean whe...

Страница 38: ...508187 01 Issue 2116 Page 38 of 51 Figure 21 Remove 5 screws if necessary either side of cabinet 1 2 3 4 5 ...

Страница 39: ...508187 01 Issue 2116 Page 39 of 51 Wiring and Sequence of Operation 045 12 070 12 090 12 090 16 110 16 110 20 COMFORT SYNC THERMOSTAT ...

Страница 40: ...se and send a signal to the integrated control The integrated control initiates a 30 second second stage recognition delay 6 At the end of the recognition delay the integrated control energizes the combustion air inducer at high speed The control also checks the high fire second stage pressure switch to make sure it is closed The high fire second stage gas valve is energized and the indoor blower ...

Страница 41: ...r begins a 5 second low speed post purge The field selected indoor blower off delay begins The indoor blower operates at the low fire heating speed 7 When the combustion air post purge period is complete the inducer and the HUM contacts are deenergized The indoor blower is de energized at the end of the off delay as well as the 120 ACC terminals Figure 22 Heating Operation with Two Stage Thermosta...

Страница 42: ...itch 2 to set sceond stage heat ON delay OFF 7 minutes ON 12 minutes ON CUT ON BOARD LINK W915 2 STAGE COMPR T STAT FURNACE TERM STRIP OUTDOOR UNIT Not required on all units 1 Heat 2 Cool with t stat with dehumidification mode NOTE Use DIP switch 2 to set sceond stage heat ON delay OFF 7 minutes ON 12 minutes ON CUT ON BOARD LINK W915 2 STAGE COMPR CUT ON BOARD LINK W914 DEHUM T STAT FURNACE TERM ...

Страница 43: ...LINK W915 2 STAGE COMPR CUT ON BOARD LINK W914 T STAT FURNACE TERM STRIP OUTDOOR UNIT o Not required on all units 2 Heat 1 Cool with t stat with dehumidification mode OFF CUT ON BOARD LINK W914 T STAT FURNACE TERM STRIP OUTDOOR UNIT o Not required on all units 2 Heat 1 Cool OFF DO NOT CUT ANY ON BOARD LINKS T STAT FURNACE TERM STRIP OUTDOOR UNIT Not required on all units NOTE Do NOT make a wire co...

Страница 44: ...RNACE TERM STRIP HEAT PUMP 67M41 Y H L Y2 D B L Y2 T T outdoor sensor Dual Fuel Two Stage Heat Pump Thermostat w dual fuel capabilities Capable of 2 stage gas heat control OFF CUT ON BOARD LINK W951 HEAT PUMP CUT ON BOARD LINK W915 2 STAGE COMPR FURNACE TERM STRIP HEAT PUMP out blue 67M41 H L Y2 D B L Y2 T T outdoor sensor T STAT Y2 NOTE Do NOT make a wire connection between the room thermostat L ...

Страница 45: ...NACE TERM STRIP HEAT PUMP 67M41 Y H L Y2 D B L Y2 T T outdoor sensor Dual Fuel Two Stage Heat Pump Thermostat w dual fuel capabilities Capable of 2 stage gas heat control with dehumidification mode OFF CUT ON BOARD LINK W914 DEHUM CUT ON BOARD LINK W951 HEAT PUMP CUT ON BOARD LINK W915 2 STAGE COMPR T STAT FURNACE TERM STRIP HEAT PUMP 67M41 H L Y2 D B L Y2 T T outdoor sensor Y2 out blue Y2 NOTE Do...

Страница 46: ...S INTERRUPTED OR T STAT IS CYCLED OFF ON FOR 3 SEC MINIMUM NO YES FIRST LOW STAGE PRESSURE SWITCH CONTACTS OPEN NO GAS VALVE OFF COMBUSTION AIR INDUCER OFF INDOOR BLOWER OFF CONTROL REMAINS UNTIL PRESSURE SWITCH IS DETECTED OPEN STATUS ERROR CODE 2 4 YES GAS VALVE OFF COMBUSTION AIR INDUCER OFF INDOOR BLOWER OFF CONTROL WILL NOT ATTEMPT SECOND STAGE OPERATION DURING THIS HEAT DEMAND FIRST STAGE OP...

Страница 47: ...N WITHIN 4 SECONDS AFTER GAS VALVE OPENS 0 19 microamps GAS VALVE OFF COMBUSTION AIR INDUCER ON INDOOR BLOWER OFF STATUS LED HEARTBEAT HAS CONTROL FAILED TO SENSE FLAME FOR FIVE CONSECUTIVE TRIES DURING A SINGLE HEAT DEMAND YES THERMOSTAT CALLS FOR HEAT STATUS LED HEARTBEAT Refer to box A on previous page YES FLAME PRESENT NO HAS CONTROL RESET IGNITION SEQUENCE FOUR 4 TIMES WATCHGUARD MODE STATUS ...

Страница 48: ...TES NO YES FIRST STAGE HEAT DEMAND SATISFIED GAS VALVE OFF COMBUSTION AIR INDUCER OFF FOLLOWING POST PURGE INDOOR BLOWER OFF WITH DELAY STATUS LED PULSE YES SECOND STAGE HEAT DEMAND SECOND STAGE HEAT DEMAND REQUIRED NO SECOND STAGE PRESSURE SWITCH CLOSED ABNORMAL FLASH CODE NOTE IF SECOND STAGE PRESSURE SWITCH WAS ORIGINALLY FOUND CLOSED ABNORMAL CODE WILL FLASH SECOND STAGE PRESSURE SWITCH CLOSED...

Страница 49: ...GE THERMOSTAT MODE DIP SWITCH SET AT SINGLE YES YES FIRST AND SECOND STAGE HEAT DEMAND SATISFIED SIMULTANEOUSLY STATUS LED HEARTBEAT YES GAS VALVE OFF COMBUSTION AIR INDUCER OFF AFTER 5 SECOND LOW SPEED POST PURGE PERIOD INDOOR BLOWER OFF DELAY INITIATED ON LOW HEAT SPEED STATUS LED HEARTBEAT DEMAND FOR HEAT SATISFIED POWER ON STAND BY STATUS LED PULSE YES SECOND STAGE HEAT DEMAND SATISFIED STATUS...

Страница 50: ...NSER FAN ENERGIZED NO IS THERE PROPER GROUND YES NO INDOOR BLOWER ENERGIZED ON FIRST STAGE COOL SPEED AFTER 2 SECOND DELAY FIRST STAGE DEMAND FOR COOL SATISFIED NO THERMOSTAT CALLS FOR SECOND STAGE COOL COMPRESSOR AND CONDENSER FAN DE ENERGIZED INDOOR BLOWER DE ENEGIZED YES INDOOR BLOWER RAMPS UP TO SECOND STAGE COOL SPEED SECOND STAGE DEMAND FOR COOL SATISFIED YES UNIT RETURNS TO FIRST STAGE COOL...

Страница 51: ...WER SWITCHES TO LOW HEAT SPEED FIRST STAGE HEAT DEMAND SATISFIED YES NO THERMOSTAT CALLS FOR SECOND STAGE HEAT YES INDOOR BLOWER SWITCHES TO HIGH HEAT SPEED AFTER 30 SECOND RECOGNITION PERIOD SECOND STAGE HEAT DEMAND SATISFIED YES YES INDOOR BLOWER RAMPS DOWN TO LOW HEAT SPEED INDOOR BLOWER RAMPS TO FIRST STAGE COOLING SPEED AFTER A 2 SECOND DELAY FIRST STAGE COOL DEMAND SATISFIED YES NO SECOND ST...

Отзывы: