Allied 4SCU20LX Скачать руководство пользователя страница 15

507523-01

Page 15 of 19

Issue  1946

Start-Up Procedure

If unit is equipped with a crankcase heater, it should 

be energized 24 hours before unit start-up to prevent 

compressor damage as a result of slugging.

 CAUTION

1.  Rotate fan to check for frozen bearings or binding.
2. 

Inspect all factory and field-installed wiring for loose 

connections.

3.  After evacuation is complete, open liquid line and 

suction line service valves to release refrigerant 

charge (contained in outdoor unit) into system.

4. 

Replace the stem caps and secure finger tight, then 

tighten an additional 1/6 of a turn.

5.  Check voltage supply at the disconnect switch. The 

voltage must be within the range listed on the unit 

nameplate. If not, do not start equipment until the 

power company has been consulted and the voltage 

condition corrected.

6.  Set thermostat for cooling demand, turn on power to 

indoor blower, and close the outdoor unit disconnect 

switch to start the unit.

7.  Recheck unit voltage with unit running. Power must be 

within range shown on unit nameplate.

Refrigerant Charging

Excessive amounts of liquid refrigerant entering the 

suction line can damage the compressor. When adding 

refrigerant, precautions must be taken to control the 

flow of liquid into the system. This can be done by using 

a liquid vaporizing adapter or manual control using a 

sight glass as indicator. 

 CAUTION

Units are factory charged with the amount of R-410A 

refrigerant indicated on the unit rating plate. This charge is 

based on a matching indoor coil and outdoor coil with 15’ 

line set. For varying lengths of line set, refer to Table 4 for 

refrigerant charge adjustment. A blank space is provided 

on the unit rating plate to list the actual field charge.

Table 4. Refrigerant Charge Adjustment

Liquid Line Set Diameter

Oz. Per 5 ft. adjust from 15 

ft. line set*

3/8 in.

3 oz. per 5 ft. 

 or 0.6 oz. per 1 ft.

* If line length is greater than 15 ft., add this amount. If line 

length is less than 15 ft., remove this amount.

Mineral oils are not compatible with R-410A. If oil must 

be added, it must be a polyolester oil.

 IMPORTANT

NOTE: 

Both  airflow  and  refrigerant  charge  must  be 

monitored for proper system set-up. It may be necessary to 

alternately check and adjust the airflow and the refrigerant 

charge.

If the system is void of refrigerant, or if the outdoor ambient 

temperature is cool, use the weigh-in method to charge the 

unit. Do this after any leaks have been repaired.
1.  Recover the refrigerant from the unit.
2.  Conduct a leak check, then evacuate as previously 

outlined.

3.  Weigh in the charge according to the total amount 

shown on the unit nameplate.

If weighing facilities are not available or if unit is being 

charged during warm weather, use one of the following 

procedures.

• 

For  systems  using  a  fixed  orifice  on  the  indoor 

evaporator and outdoor temperatures above 

65°F

 – charge using the superheat method and table 

provided on the unit access panel.

•  For systems using a TXV on the indoor evaporator 

and outdoor temperature above 60°F

 – charge in 

cooling mode using the subcooling method and table 

provided on the unit access panel.

•  For systems below 60°F

 – charge in heating mode 

using the subcooling method and table provided on 

the unit access panel. Attach low pressure gauge 

hose to auxiliary service port to access suction side in 

heating mode.

NOTE: 

All unit table values are based on 70 to 80°F 

indoor return air temperature for cooling mode, and 

65

°

F to 75°F return air temperature for heat mode.

Содержание 4SCU20LX

Страница 1: ...e personal injury or death WARNING ELECTRICAL SHOCK HAZARD Risk of electrical shock Disconnect all remote power supplies before installing or servicing any portion of the system Failure to disconnect power supplies can result in property damage personal injury or death WARNING Sharp metal edges can cause injury When installing the unit use care to avoid sharp edges WARNING Read this entire instruc...

Страница 2: ... unit away from windows patios decks etc where unit operation sounds may disturb customer Leave some slack between structure and unit to absorb vibration Place a sound absorbing material such as Isomode under the unit if it will be installed in a location or position that will transmit sound or vibration to the living area or adjacent buildings In heavy snow areas do not locate the unit where drif...

Страница 3: ...ould be unobstructed by a wall or other barrier Table 2 Clearances 30 around Control Box 24 6 NOTE See Table 2 for specific minimum clearance guidelines Figure 2 DO LOCATE THE UNIT With proper clearances on sides and top of unit On a solid level foundation or pad unit must be level to within 1 4 in ft per compressor manufacturer specifications To minimize refrigerant line lengths DO NOT LOCATE THE...

Страница 4: ... important for proper system operation and reliability If the drier is shipped loose it must be installed by the installer in the field Unit warranty will be void if the drier is not installed Installation of Line Sets DO NOT fasten liquid or suction lines in direct contact with the floor or ceiling joist Use an insulated or suspension type of hanger Keep both lines separate and always insulate th...

Страница 5: ...E USED FOR FLUSHING Positioned to deliver liquid refrigerant LIQUID LINE SERVICE VALVE INLET DISCHARGE TANK RETURN CLOSED OPENED RECOVERY CYLINDER RECOVERY MACHINE NEW OUTDOOR UNIT VAPOR LINE SERVICE VALVE VAPOR LIQUID 1 A B C D A Cylinder with clean R 410A positioned to deliver liquid refrigerant to the vapor service valve B Refrigerant gauge set low side to the liquid line valve C Refrigerant ga...

Страница 6: ...Shown Sensing bulb insulation is required if mounted external to the coil casing sensing bulb installation for bulb positioning STUB END TEFLON RING LIQUID LINE ASSEMBLY WITH BRASS NUT DISTRIBUTOR ASSEMBLY 3 Install one of the provided Teflon rings around the stubbed end of the check expansion valve and lightly lubricate the connector threads and expose surface of the Teflon ring with refrigerant ...

Страница 7: ...ssure side to liquid line service valve service port B Connect gauge set center port to bottle of nitrogen with regulator C Remove core from valve in vapor line service port to allow nitrogen to escape NITROGEN HIGH LOW USE REGULATOR TO FLOW NITROGEN AT 1 TO 2 PSIG B A C WHEN BRAZING LINE SET TO SERVICE VALVES POINT FLAME AWAY FROM SERVICE VALVE Flow regulated nitrogen at 1 to 2 psig through the l...

Страница 8: ...VES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WRAP SERVICE VALVES To help protect service valve seals during brazing wrap water saturated cloths around service valve bodies and copper tube stubs Use additionalwater saturated cloths underneath the valve body to protect the base paint 4 FLOW NITROGEN Flow regulated nitrogen at 1 to 2 psig through the refrigeration gauge set int...

Страница 9: ...he valve on the high side of the manifold gauge set in order to pressurize the line set and the indoor unit E After a few minutes open one of the service valve ports and verify that the refrigerant added to the system earlier is measurable with a leak detector F After the line set has been connected to the indoor and outdoor units check the line set connections and indoor unit for leaks Use the fo...

Страница 10: ...uid refrigerant Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and indoor unit G Perform the following Close manifold gauge valves Shut off HFC 410A cylinder Reinstall service valve cores by removing manifold hose from service valve Quickly install cores with core tool while maintaining a positive system pressure Replace stem caps and finger tighten them t...

Страница 11: ...ench with a hex head extension to back the stem out counterclockwise as far as it will go Use a 3 16 hex head extension for liquid line service valves and a 5 16 extension for suction line service valves 3 Replace the stem cap Tighten finger tight then tighten an additional 1 6 turn To Close Liquid or Suction Line Service Valve 1 Remove the stem cap with an adjustable wrench 2 Use a service wrench...

Страница 12: ...ructions shipped with room thermostat Generally the thermostat should not be exposed to sunlight drafts or vibration and should not be mounted on exterior walls Low voltage wiring must be separated from high voltage wiring WARNING Low voltage connections should be in accordance to the wiring diagram Alarms Alarm information is provided on the outdoor unit access panel and in the Comfort Sync Wi Fi...

Страница 13: ... C Terminal OUTDOOR UNIT PROVIDED RAST 6 PIN CONNECTOR CONNECTS TO RAST 6 PIN CONNECTOR ROUTE CONTROL WIRING THROUGH GROMMET AND SECURE WITH CABLE TIE GROMMET AND CABLE TIE USE WATERTIGHT CONDUIT FOR HIGH VOLTAGE CONNECT CONDUIT TO CUTOUT AND ROUTE HIGH VOLTAGE WIRING INDOOR CONTROL Thermostat Figure 7 Control Wiring ...

Страница 14: ...Page 14 of 19 507523 01 Issue 1946 Figure 8 Control Board 7 SEGMENT DISPLAY PUSH BUTTON ...

Страница 15: ...t A blank space is provided on the unit rating plate to list the actual field charge Table 4 Refrigerant Charge Adjustment Liquid Line Set Diameter Oz Per 5 ft adjust from 15 ft line set 3 8 in 3 oz per 5 ft or 0 6 oz per 1 ft If line length is greater than 15 ft add this amount If line length is less than 15 ft remove this amount Mineral oils are not compatible with R 410A If oil must be added it...

Страница 16: ...nser Coils Grass cuttings leaves dirt dust lint from clothes dryers and foliage from trees can be drawn into coils by movement of the air Clogged condenser coils will lower the efficiency of your unit and could cause damage to the condenser Periodically debris should be brushed from the condenser coils Use a soft bristle brush with light pressure only DO NOT damage or bend condenser coil fins Dama...

Страница 17: ...anty replacement parts are required the warranty must be processed through a qualified distribution location Homeowner Information ELECTRICAL SHOCK HAZARD Turn OFF electric power to unit before performing any maintenance or removing panels or doors FAILURE TO DO SO COULD RESULT IN BODILY INJURY OR DEATH WARNING Thermostat Operation The wall mounted thermostat controls your air conditioner The ther...

Страница 18: ...T GRAY GRAY GRAY GRAY RED GRAY RED GRAY RED BLACK YELLOW BLUE BLACK THERMAL PROTECTION SWITCH GRAY GRAY RED BLACK BLUE BROWN NOTES 1 NOTE FOR USE WITH COPPER CONDUCTORS ONLY REFER TO UNIT RATING PLATE FOR MINIMUM CIRCUIT AMPICITY AND MAXIMUM OVERCURRENT PROTECTION SIZE 2 WARNING ELECTRIC SHOCK HAZARD CAN CAUSE INJURY OR DEATH UNIT MUST BE GROUNDED IN ACCORDANCE WITH NATIONAL AND LOCAL CODES 3 REFE...

Страница 19: ...IMUM CIRCUIT AMPICITY AND MAXIMUM OVERCURRENT PROTECTION SIZE 2 WARNING ELECTRIC SHOCK HAZARD CAN CAUSE INJURY OR DEATH UNIT MUST BE GROUNDED IN ACCORDANCE WITH NATIONAL AND LOCAL CODES 3 REFER TO COMPRESSOR IN UNIT FOR ACTUAL TERMINAL ARRANGEMENT 4 NOTE IF ANY WIRE IN THE APPLIANCE IS REPLACED IT MUST BE REPLACED WITH WIRE OF LIKE SIZE RATING INSULATION THICKNESS AND TERMINATION U W V 1 2 GRAY GR...

Отзывы: