508226-01
Issue 2135
Page 5 of 38
Technical Specifications - 4AC13B/L*-7,8
MODEL NUMBER GUIDE
PHYSICAL AND ELECTRICAL DATA
Model
Voltage/Hz/Phase
Voltage
Range
Min.
Circuit
Amp.
Max. Over
Current
Device
(amps)
†
Compressor
Fan Motor
Refrig.
Charge
(oz) ††
Rated Load
(amps)
Locked
Rotor
(amps)
Rated
Load
(amps)
Rated
HP
Nom.
RPM
4AC13*18P-7,8
208-230/60/1
197-253
10.9
15
8.1
39
0.7
1/10
1010
62
4AC13*24P-7,8
208-230/60/1
197-253
14.1
20
10.7
53
0.7
1/10
1010
63
4AC13*30P-7,8
208-230/60/1
197-253
15.6
25
11.6
59
1.1
1/5
1090
82
4AC13*36P-7,8
208-230/60/1
197-253
20.1
35
15.2
70
1.1
1/5
1090
84
4AC13*42P-7,8
208-230/60/1
197-253
28.1
45
21.1
90
1.7
1/4
825
104
4AC13*48P-7,8
208-230/60/1
197-253
31.9
50
24.1
100
1.7
1/4
825
124
4AC13*60P-7,8
208-230/60/1
197-253
29.4
50
22.1
120
1.7
1/4
825
144
† Overcurrent protection device
† † Factory charge adequate for 15 feet of line set. Adjust per installation instructions.
UNIT DIMENSIONS (IN.) & SOUND RATINGS
Model No.
Dimensions
Shipping
Weight
(lbs.)
Sound
Ratings
(dBA)
A - Width
B - Depth
C - Height
Louvered
4AC13*18P-7,8
24.25
24.25
25
136
74
4AC13*24P-7,8
24.25
24.25
25
137
74
4AC13*30P-7,8
24.25
24.25
29
147
74
4AC13*36P-7,8
24.25
24.25
29
149
74
4AC13*42P-7,8
28.25
28.25
29
194
79
4AC13*48P-7,8
28.25
28.25
33
192
79
4AC13*60P-7,8
28.25
28.25
29
205
80
Note:
Weights listed are unit weights with packaging
Dimensions listed are unit sizes w/o packaging
Minor Revision Code
Major Revision Code
Electrical
P - 208 - 230v/60hz/1Ph
Tonnage
18, 24, 30, 36, 42, 48, 60
Refrigerant
4 = R410A
AC
Air Conditioner
SEER
13
Tier
B = Wire Guard
L =
Louvered
4 AC 13 L 24 P - 7 A
Содержание 4AC13B
Страница 31: ...508226 01 Issue 2135 Page 31 of 38 Figure 13 Wiring Diagram Wiring Diagram ...
Страница 35: ...508226 01 Issue 2135 Page 35 of 38 Charge Labels Figure 14 4AC13 10 11 ...
Страница 36: ...508226 01 Issue 2135 Page 36 of 38 Figure 15 4AC13 7 8 ...
Страница 37: ...508226 01 Issue 2135 Page 37 of 38 Figure 16 4AC13 3 4 5 6 ...