508226-01
Issue 2135
Page 3 of 38
SOUND RATINGS
Model
Sound Power
1
Estimated Sound Pressure (dBA)
2
Approximate Distance
3
3.3 Feet
(1 Meter)
6.6 Feet
(2 Meters)
9.8 Feet
(3 Meters)
4AC13*18P-10/11
74
66
60
56
4AC13*24P-10/11
74
66
60
56
4AC13*30P-10/11
74
66
60
56
4AC13*36P-10/11
74
66
60
56
4AC13*42P-10/11
79
71
65
61
4AC13*48P-10/11
79
71
65
61
4AC13*60P-10/11
80
72
66
62
1 Rated in accordance with AHRI standard 270 (2015). AHRI Standard 270 establishes a method of rating outdoor unitary equipment in terms of Sound Power.
2 Rated in accordance with AHRI standard 275 (2010). AHRI Standard 275 provides the calculations for estimating the A-Weighted Sound Pressure at a given distance
from the equipment. That is a more useful number because that is what humans will hear.
3 Based only on distance factor; other factors may change this value such as:
- Unit location (reflective surfaces adjacent to the unit)
- Barrier shielding sources
- Sound path/elevation
- Outside noise sources
ACCESSORIES
System Accessory
Where Used
Kit Number
Purpose
Liquid Line solenoid
All models
60M52
Prevents liquid migration to the compressor especially for high liquid riser applications
Low Ambient (cooling operation)
All models
34M72
Enables cooling demand down to 30 °F. Will require freeze stat, CC heater and TXV
Compressor Short Cycle Protector
All models
47J27
Delays compressor start 5-7 minutes to prevent short cycling
Hard Start
18
10J42
Scroll compressors usually do not require hard start; maybe needed for utility brown-out
or low voltage areas
24 thru 60
88M91
Crankcase Heater
18, 24, 30, 36
93M04
Prevents liquid migration to compressor in cold weather
42, 48, 60
93M05
Sound Cover
18, 24, 30, 36
14W00
Lowers compressor sound level
42, 48, 60
14W01
Loss of Charge Kit
All models
84M23
Protects the compressor if refrigerant charge is too low
Additional System Accessories (indoor section)
TXV Kit
18, 24, 30
H4TXV01
TXVs provide superior refrigerant flow control, comfort and efficiency compared to
pistons
36, 42, 48
H4TXV02
60
H4TXV03
Outdoor Thermostat - Electric Heat
All models
10Z23
Prevents electric heat operation above specific ambient conditions
Outdoor Thermostat - Mounting Box
All models
31461
Mounting box for outdoor thermostat
Freezestat
All models
93G35
Protects the compressor at low suction pressure conditions
Overflow Switch
All models
11U75
Turn the system off, if condensate water overflows due to clogged drain pipes
Blower Time Delay
All models
58M81
Improves system efficiency and comfort
Single Point Power Supply
All models
21H39
Provide single power source in one junction box
Auxiliary Blower Relay
All models
85W66
Maybe required to select multiple indoor blower speeds
Содержание 4AC13B
Страница 31: ...508226 01 Issue 2135 Page 31 of 38 Figure 13 Wiring Diagram Wiring Diagram ...
Страница 35: ...508226 01 Issue 2135 Page 35 of 38 Charge Labels Figure 14 4AC13 10 11 ...
Страница 36: ...508226 01 Issue 2135 Page 36 of 38 Figure 15 4AC13 7 8 ...
Страница 37: ...508226 01 Issue 2135 Page 37 of 38 Figure 16 4AC13 3 4 5 6 ...