AT-D3726XL Addendum
3
Warning
When installing this equipment, always ensure that the frame ground connection
is installed first and disconnected last.
5.
Connect the positive feed to the terminal block (plus).
6.
Connect the negative feed to the terminal block marked - (minus).
7.
Caution: "Safety Hazard"- Check to see if there are any exposed copper
strands coming from the installed wire. When this installation is done correctly
there should be no exposed copper wire strands extending from the terminal
block. Any exposed wiring can conduct harmful levels of electricity to persons
touching the wires.
8.
Secure the tray supply cable near the rack framework using multiple cable ties
to minimize the chance of the connections being disturbed by casual contact
with the wiring. Use at least four cable ties separated four inches apart with
the first one located within six inches of the terminal block.
Note
This system will work with a positive grounded or negative grounded DC system.
DC INPUT
FOR CENTRALIZED DC
POWER CONNECTION,
INSTALL ONLY IN A
RESTRICTED AREA
36-60VDC , 1.0A