Return Air - Upflow Applications
Return air can be brought in through the bottom or either
side of the furnace installed in an upflow application. If the
furnace is installed on a platform with bottom return, make
an airtight seal between the bottom of the furnace and the
platform to ensure that the furnace operates properly and
safely. The furnace is equipped with a removable bottom
panel to facilitate installation.
Markings are provided on both sides of the furnace cabinet
for installations that require side return air. Cut the furnace
cabinet at the maximum dimensions shown on page 2.
NOTE:
20C and 20D units that require air volumes over
1800 cfm (850 L/s) must have
one of
the following:
1.
Single side return air with transition to
accommodate 20
x 25 x 1
in. (508
x 635 x 25
mm)
cleanable air filter. (Required to maintain proper air
velocity.)
See
Figure 9.
2.
Single side return air with optional return airbase.
See
Figure 10.
3.
Bottom return air.
4.
Return air from both sides.
5.
Bottom and
one
side return air.
Optional Return Air Base
(Upflow Applications Only - For use with A, B, C and D cabinets))
NOTE:
Optional Side Return Air Filter Kits are not for use with Return Air Base.
1 Both the unit return air opening and the base return air opening must be covered by a single plenum or IAQ cabinet.
Minimum unit side return air opening dimensions for units requiring 1800 cfm or more of air (W x H): 23 x 11 in. (584 x 279 mm).
The opening can be cut as needed to accommodate plenum or IAQ cabinet while maintaining dimensions shown.
Side return air openings must be cut in the field. There are cutting guides stenciled on the cabinet for the side return air opening.
The size of the opening must not extend beyond the markings on the furnace cabinet.
² To minimize pressure drop, the largest opening height possible (up to 14 inches) is preferred.
FRONT VIEW
Figure 10
Figure 9
Single Side Return Air
(with transition and filter)
Содержание 80G1UH
Страница 3: ...506526 01 Page 3 of 39 Issue 1031 A80UH 80G1UH Expanded View Figure 1...
Страница 27: ...506526 01 Page 27 of 39 Issue 1031 Wiring Diagram Figure 32...
Страница 38: ...506526 01 Page 38 of 39 Issue 1031 START UP PERFORMANCE CHECK LIST UNIT SET UP...
Страница 39: ...506526 01 Page 39 of 39 Issue 1031 UNIT OPERATION...