All wiring should be done in accordance with the
National Electrical Code, ANSI/NFPA No. 70 (latest
edition);  Canadian Electrical Code Part 1, CSA C22.1
(latest edition); or local codes where they prevail. 

Use

wiring with a temperature limitation of 75°C minimum. Run
the 208 or 230 volt, 60 hertz electric power supply through a
fused disconnect switch to the control box of the unit and
connect as shown in the wiring diagram located on the inside
of the control access panel.
Power supply to the unit must be N.E.C. Class 1, and must

comply with all applicable codes. A fused disconnect switch
should be field provided for the unit.  The switch must be
separate from all other circuits.  If any of the wire supplied
with the unit must be replaced, replacement wire must be of
the type shown on the wiring diagram.  Electrical wiring must
be sized to carry minimum circuit ampacity marked on the
unit. 

 Use copper conductors only.

  Each unit must be

wired with a separate branch circuit and be properly fused.

Thermostat

The room thermostat should be located on an inside wall where
it will not be subject to drafts, sun exposure, or heat from
electrical fixtures or appliances.  Follow the manufacturer’s
instructions enclosed with thermostat for general installation
procedure.  Color-coded insulated wires (#18 AWG) should
be used to connect the thermostat to the unit.

Four wires are required for cooling.  The heat anticipator
setting is 0.75 amp.

When connecting electrical power and control wiring to
the unit, waterproof type connectors must be used so that
water or moisture cannot be drawn into the unit during
normal operation.

 CAUTION

Compressor

Units are shipped with compressor mountings factory-
adjusted and ready for operation.

Caution: Do not loosen compressor mounting bolts.

LPG/Propane Units, Tanks, and Piping

Units are shipped equipped for natural gas, but can be
converted to LPG/propane in the field by an approved
licensed technician.  If conversion is required, use the
approved conversion kit.

When converting a low NO

x

 unit (designated by an L in the

model number) to propane, 

the NO

x

 inserts

 

must

 

be

removed

.  After removing the burners, remove the screw

holding each insert and pull the insert from the combustion
chamber.  The screws 

must be reinstalled

 in the vest panel

after the inserts are removed.

All LPG/propane gas equipment must conform to the safety
standards of the National Fire Protection Association.

For satisfactory operation, LPG/propane gas pressure must
be a minimum of 11" w.c. at the unit under full load.

Complete information regarding tank sizing for vaporization,
recommended regulator settings, and pipe sizing is available
from most regulator manufacturers and LPG/propane gas
suppliers.

Check all connections for leaks when piping is completed,
using a soapy solution. 

 Some soaps used for leak detection

are corrosive to certain metals.  Carefully rinse piping
thoroughly after completing leak detection.
Electrical Wiring (See Figures 4 & 5)

Power Wiring

If 208 volt is supplied, transformer connections must be made.

Line Voltage 208/230 Volts

Figure 5

GROUND
    LUG

CONTACTOR

FIELD-SUPPLIED
        FUSED
   DISCONNECT SINGLE

PHASE
POWER
SUPPLY

Содержание 506271-01

Страница 1: ...also be followed Failure to do so may result in equipment damage personal injury and improper performance of the unit WARNING The installation of the furnace wiring warm air ducts venting etc must con...

Страница 2: ...from water 2 Condenser coils must have an unlimited supply of air 3 For ground level installation use a level prefabricated pad or use a level concrete slab Do not tie the slab to the building founda...

Страница 3: ...r shrubs to obstruct condenser air discharge outlet combustion air inlet or vent outlet Before lifting a unit make sure that the weight is distributed equally on the cables so that it will lift evenly...

Страница 4: ...e common venting system 2 Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction leakage corrosion or other deficiencies which could...

Страница 5: ...d with the local gas utility For temperature rise of unit see unit rating plate Condensate Drain This package unit is equipped with a 3 4 FPT coupling for condensate line connection Plumbing must conf...

Страница 6: ...sure testing of that system at test pressures in excess of 1 2 PSIG 3 48kPa A1 8 N P T plugged tapping accessible for test gauge connections must be installed immediately upstream of the gas supply co...

Страница 7: ...l power and control wiring to the unit waterproof type connectors must be used so that water or moisture cannot be drawn into the unit during normal operation CAUTION Compressor Units are shipped with...

Страница 8: ...rt Check List After the entire control circuit has been energized and the heating section is operating make the following checks 1 Check for gas leaks using soapy solution in the unit piping as well a...

Страница 9: ...correctly check manifold pressure outlet side of the gas valve It should be 10 to 10 5 w c pressure for LPG propane The furnace is designed to obtain rated input at 10 w c manifold pressure for propa...

Страница 10: ...fan motor and blower motor Blower Delay Cooling The circulating air blower is controlled by a timing circuit in the integrated blower ignition control Timings are not adjustable Blower ON delay is 5 s...

Страница 11: ...s the main gas valve To reset push the button on top of the switch Auxiliary Limit This control is located in the side of the circulation air blower housing The switch opens and shuts off the blower i...

Страница 12: ...down the heat exchanger tubes from the flue collector end 7 If soot buildup is excessive remove the vent motor and clean the wheel and housing Run the wire brush down the flue extension at the outlet...

Страница 13: ...506271 01 Page 13 of 14 Issue 0921 Wiring Diagram Single Phase Figure 8...

Страница 14: ...Page 14 of 14 506271 01 Issue 0921 NOTES...

Отзывы: