6. APPENDIX
6.2 Cable specification
1. SINGLE PHASE UNIT
NAME PLATE
MAXIMUM
CURRENT
PHASE LINE
EARTH LINE
MCB
CREEPAGE PROTECTOR
SIGNAL LINE
No more than 10A
2 X 1.5mm
2
1.5mm
2
20A 30mA less than 0.1 sec
n X 0.5mm
2
10~16A
2 X 2.5mm
2
2.5mm
2
32A 30mA less than 0.1 sec
16~25A
2 X 4mm
2
4mm
2
40A 30mA less than 0.1 sec
25~32A
2 X 6mm
2
6mm
2
40A 30mA less than 0.1 sec
32~4QA
2 X 10mm
2
10mm
2
63A 30mA less than 0.1 sec
40~63A
2 X 16mm
2
16mm
2
80A 30mA less than 0.1 sec
63~75A
2 X 25mm
2
25mm
2
100A 30mA less than 0.1 sec
75~1Q1A
2 X 25mm
2
25mm
2
125A 30mA less than 0.1 sec
101~123A
2 X 35mm
2
35mm
2
160A 30mA less than 0.1 sec
123~148A
2 X 50mm
2
50mm
2
225A 30mA less than 0.1 sec
148~186A
2 X 70mm
2
70mm
2
250A 30mA less than 0.1 sec
186~224A
2 X 95mm
2
95mm
2
280A 30mA less than 0.1 sec
2. THREE PHASE UNIT
NAME PLATE
MAXIMUM
CURRENT
PHASE LINE
EARTH LINE
MCB
CREEPAGE PROTECTOR
SIGNAL LINE
No more than 10A
3 X 1.5mm
2
1.5mm
2
20A 30mA less than 0.1 sec
n X 0.5mm
2
10~16A
3 X 2.5mm
2
2.5mm
2
32A 30mA less than 0.1 sec
16~25A
3 X 4mm
2
4mm
2
40A 30mA less than 0.1 sec
25~32A
3 X 6mm
2
6mm
2
40A 30mA less than 0.1 sec
32~4QA
3 X 10mm
2
10mm
2
63A 30mA less than 0.1 sec
40~63A
3 X 16mm
2
16mm
2
80A 30mA less than 0.1 sec
63~75A
3 X 25mm
2
25mm
2
100A 30mA less than 0.1 sec
75~1Q1A
3 X 25mm
2
25mm
2
125A 30mA less than 0.1 sec
101~123A
3 X 35mm
2
35mm
2
160A 30mA less than 0.1 sec
123~148A
3 X 50mm
2
50mm
2
225A 30mA less than 0.1 sec
148~186A
3 X 70mm
2
70mm
2
250A 30mA less than 0.1 sec
186~224A
3 X 95mm
2
95mm
2
280A 30mA less than 0.1 sec
If the unit is installed outdoors, please use a UV protected cable.