Exhaust System
IMPORTANT: Keep exhaust duct as short as
possible.
NOTE: Be certain old ducts are cleaned before
installing your new dryer unit.
For best drying results, recommended maximum
length of exhaust system is shown in
Table 2
.
To prevent backdraft when dryer unit is not in
operation, outer end of exhaust pipe must have a
weather hood with hinged dampers (obtain locally).
NOTE: Weather hood should be installed at least
12 inches (30.5 cm) above the ground. Larger
clearances may be necessary in areas where heavy
snowfall can occur.
Number of
90° Elbows
Weather Hood Type
Recommended
Use Only for Short Run Installations
Maximum length of 4" (10.2 cm) diameter rigid metal duct
0
65 feet (19.8 m)
55 feet (16.8 m)
1
55 feet (16.8 m)
47 feet (14.3 m)
2
47 feet (14.3 m)
41 feet (12.5 m)
3
36 feet (11.0 m)
30 feet (9.1 m)
4
28 feet (8.5 m)
22 feet (6.7 m)
Maximum length of 4" (10.2 cm) diameter flexible metal duct
0
45 feet (13.7 m)
35 feet (10.7 m)
1
35 feet (10.7 m)
27 feet (8.2 m)
2
30 feet (9.1 m)
21 feet (6.4 m)
3
25 feet (7.6 m)
17 feet (5.2 m)
4
20 feet (6.1 m)
15 feet (4.5 m)
NOTE: Deduct 6 feet (1.8 m) for each additional elbow.
Table 2
4"
(10.2 cm)
4"
(10.2 cm)
D673I
2-1/2"
(6.35 cm)
D802I
Содержание Stacked Clothes Dryer
Страница 2: ......
Страница 4: ...Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 2 510975 Notes...
Страница 8: ...Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 510975 6 Notes...
Страница 54: ...Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 510975 52 Notes...
Страница 60: ......
Страница 62: ...Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 60 510975 SP Notas...
Страница 66: ...Copyright Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT 510975 SP 64 Notas...
Страница 117: ......