Tie-in to Existing Floor (refer to
)
CHM2390N_SVG
1
2
B
C
D
A
4
5
3
1.
Existing Floor
2.
3500 PSI (minimum) Concrete
3.
Reinforcing Bar
4.
Perimeter Reinforcing Bar
5.
Compacted Fill (minimum 6 in. [152 mm] )
Figure 21
Tie-in to Existing Floor, in. [mm]
Description
20-30
40-60 (F-speed)
40-60 (V-speed) /
80-100 (F-speed)
80-100 (V-
speed)
A
Required thickness of existing
floor (minimum)
4 [102]
4 [102]
6 [152]
9 [229]
B
Total depth of foundation (con-
crete plus 6 in. [152 mm] fill)
(minimum)
10 [254]
10 [254]
12 [305]
15 [381]
C
Distance between reinforcing
bars (minimum)
12 [305]
12 [305]
12 [305]
12 [305]
D
Length of reinforcing bar ex-
tending into existing floor (mini-
mum)
2.5 [64]
2.5 [64]
2.5 [64]
2.5 [64]
Table 23
Installation
©
Copyright, Alliance Laundry Systems LLC -
DO NOT COPY or TRANSMIT
58
Part No. F8619501ENR11