Gas Requirements
M414905
36
© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT
Gas Supply Pipe Sizing and Looping
Figure 18
TMB2126N
1
Gas furnace (120,000 Btu/hr.)
7
Minimum Pipe Size is 0.5 in. (12.7 mm)
2
Gas water heaters (400,000 Btu/hr. each)
8
25 ft. (7.6 m)
3
Gas space heaters (70,000 Btu/hr. each)
9
Main regulator
4
Sediment traps, supply pressure taps and
10
Gas meter
shut-off valves. Refer to
11
Pressure regulator (if required)
5
1 in. (25.4 mm) gas pipe loop
12
50 pound tumblers (120,000 Btu/hr each)
6
19 ft. (5.8 m)
75 pound tumblers (165,000 Btu/hr each)
F75 pound tumblers (215,000 Btu/hr each)
SAMPLE CALCULATIONS:
Equivalent length
= Total length of main gas supply pipe to the far end of the tumblers.
= 25 ft. + 19 ft. (7.6 m + 5.8 m) gas supply pipe
= 44 ft. (13.4 m) Total Gas Line
Total Btu/hr.
= The sum of the Btu/hr. of all 50 pound tumblers being fed by the main gas supply pipe.
= 9
x
120,000
= 1,080,000
Btu/hr.
Using
, the main supply pipe diameter should be 2 in. (51 mm).
IMPORTANT: Gas loop piping must be installed as illustrated to equalize gas pressure for all tumblers
connected to single gas service. Other gas using appliances should be connected upstream from loop.
1
2
3
4
5
6
7
8
9
M
9
12
8
6
3
2
1
10
11
7
5
4