Publication 1747-UM011G-EN-P - June 2008
62
System Installation Recommendations
•
Use 2.54 cm (1 in.) copper braid or 5.2 mm
2
(#10 AWG) copper wire to
connect each chassis, the enclosure, and a central ground bus mounted
on the back-panel.
•
Use a steel enclosure to guard against electromagnetic interference
(EMI).
•
Make sure the enclosure door viewing window is a laminated screen or a
conductive optical substrate (to block EMI).
•
Install a bonding wire for electrical contact between the door and the
enclosure; do not rely on the hinge.
Connect Ground Bus to Grounding-Electrode System
The grounding-electrode system is at earth-ground potential and is the central
ground for all electrical equipment and ac power within any facility. Use a
grounding-electrode conductor to connect the ground bus to the
grounding-electrode system. Use at minimum 8.3 mm
2
(#8 AWG) copper wire
for the grounding-electrode conductor to guard against EMI. The National
Electrical Code specifies safety requirements for the grounding-electrode
conductor.
Europe:
Reference EN 60204 for safety information on grounding. Also, refer
to Allen-Bradley Programmable Controller Grounding and Wiring Guidelines,
IMPORTANT
Do not lay one ground lug directly on top of the other; this type
of connection can become loose due to compression of the
metal lugs. Place the first lug between a star washer and a nut
with a captive star washer. After tightening the nut, place the
second lug between the first nut and a second nut with a
captive star washer.
Equipment Grounding Conductors
Ground Lug
Grounding-Electrode
Conductor to
Grounding-Electrode
System
Tapped Hole
Ground Bus
Ground Bus
Mounting
Bolt - Size M5 or M6 (4.826
mm or 5.48 mm) hardware
Internal star washer - Size
M5 or M6 (#10 or #12)
Содержание SLC 500
Страница 4: ...Publication 1747 UM011G EN P June 2008 4 Summary of Changes Notes ...
Страница 12: ...Publication 1747 UM011G EN P June 2008 12 Table of Contents Glossary Index ...
Страница 26: ...Publication 1747 UM011G EN P June 2008 26 Quick Start for Experienced Users Notes ...
Страница 54: ...Publication 1747 UM011G EN P June 2008 54 Selecting Your Hardware Components Notes ...
Страница 74: ...Publication 1747 UM011G EN P June 2008 74 System Installation Recommendations Notes ...
Страница 110: ...Publication 1747 UM011G EN P June 2008 110 Installing Your Hardware Components Notes ...
Страница 168: ...Publication 1747 UM011G EN P June 2008 168 Troubleshooting Notes ...
Страница 174: ...Publication 1747 UM011G EN P June 2008 174 Replacement Parts Notes ...
Страница 180: ...Publication 1747 UM011G EN P June 2008 180 Specifications ...
Страница 200: ...Publication 1747 UM011G EN P June 2008 200 Setting Up the DH 485 Network Notes ...
Страница 260: ...Publication 1747 UM011G EN P June 2008 260 Communicating with Devices on an Ethernet Network Notes ...
Страница 270: ...Publication 1747 UM011G EN P June 2008 270 Calculating Heat Dissipation for the SLC 500 Control System Notes ...
Страница 286: ...Publication 1747 UM011G EN P June 2008 286 Glossary Notes ...