Publication 1747-UM011G-EN-P - June 2008
Starting Up Your Control System
123
is to open the circuit at a point between the motor starter and the
relay contact.
3. Initialize and Test Your
Processor
When you are certain that machine motion cannot occur with the
controller energized, you may begin by initializing the processor using
the following steps.
1.
Energize the chassis power supply. If power is supplied to the
controller and the installation is correct, the initial factory
conditions for all processors are provided in the following table.
ATTENTION
Machine motion during system checkout can be hazardous to
personnel. During the checkout procedures 3, 4, 5, and 6, you
must disconnect all devices that, when energized, might cause
machine motion.
Processor Name
DEFAULT
Mode
Program mode or
Fault mode
(S:1/0 to S:1/4 = 0 0001) or
(S:1/0 to S:1/4 = 0.0001 and S:1/13 = 1)
Watchdog values
100 ms
S:3H = 0000 1010
I/O slot enables
ALL ENABLED
S:11/1 through S:12/14 set to 1
Node address
(except SLC 5/04 and 5/05)
1
Channel 1 = DH485
S:15L = 0000 0001
Communication rate
(except SLC 5/04 and 5/05)
19.2 Kbaud
Channel 1 = DH485
S:15H = 0000 0100
SLC 5/03, SLC 5/04, and
SLC 5/05 processor only
Channel 0
configuration
DF1 Full-duplex
No Handshaking
19.2 KBaud
CRC Error Check
Duplicate Detect On
No Parity
SLC 5/04 processor only
Channel 1
configuration
DH+
57.6 KBaud
Default Node Address = 1
SLC 5/05 processor only
Channel 1
configuration
Ethernet
(1)
10 Mbps
(1)
Configuring with BOOTP enabled so that a BOOTP server on the network can automatically provide the SLC 5/05
processor with the configuration necessary to start communicating over Ethernet. See appendix G for more
information.
Содержание SLC 500
Страница 4: ...Publication 1747 UM011G EN P June 2008 4 Summary of Changes Notes ...
Страница 12: ...Publication 1747 UM011G EN P June 2008 12 Table of Contents Glossary Index ...
Страница 26: ...Publication 1747 UM011G EN P June 2008 26 Quick Start for Experienced Users Notes ...
Страница 54: ...Publication 1747 UM011G EN P June 2008 54 Selecting Your Hardware Components Notes ...
Страница 74: ...Publication 1747 UM011G EN P June 2008 74 System Installation Recommendations Notes ...
Страница 110: ...Publication 1747 UM011G EN P June 2008 110 Installing Your Hardware Components Notes ...
Страница 168: ...Publication 1747 UM011G EN P June 2008 168 Troubleshooting Notes ...
Страница 174: ...Publication 1747 UM011G EN P June 2008 174 Replacement Parts Notes ...
Страница 180: ...Publication 1747 UM011G EN P June 2008 180 Specifications ...
Страница 200: ...Publication 1747 UM011G EN P June 2008 200 Setting Up the DH 485 Network Notes ...
Страница 260: ...Publication 1747 UM011G EN P June 2008 260 Communicating with Devices on an Ethernet Network Notes ...
Страница 270: ...Publication 1747 UM011G EN P June 2008 270 Calculating Heat Dissipation for the SLC 500 Control System Notes ...
Страница 286: ...Publication 1747 UM011G EN P June 2008 286 Glossary Notes ...