Rockwell Automation Publication 440T-IN016C-EN-P - January 2018

3

Prosafe Electronic Time Delay Unit

Examples

For a 2 minute delay, start the short range configuration and set the 

range to 7 for a 300 second maximum and the time to 4 for 40% of the 

maximum.
For a 30 minute delay, start in the long range configuration and set the 

range to 6 for a 3000 second maximum and the time to 6 for 60% of the 

maximum.

Upon Installation

Lubricate code barrel assembly with light oil or spray, for example, 

WD-40® or alternative product suitable for application. Check for 

correct operation.

Maintenance

Every Week

Check the correct operation of the switching circuit. Also check for 

signs of abuse or tampering. Inspect the unit for damage. Replace the 

unit if damage is apparent.

At Least Every Six Months

Isolate all power. Check for any sign of wear or damage, for example, 

cam assembly wear or contact oxidization and replace if apparent. Clean 

out any accumulation of fine dirt, and so on. Lubricate code barrel 

assembly with light oil or spray, for example WD-40 or alternative 

product suitable for application.
Assessment of the operating environment can require the unit to be 

lubricated more frequently. Reinstate the power and check for correct 

operation.

Repair

If there is any malfunction or damage, do not attempt to repair it. 

Replace the unit before machine operation is allowed.

Declaration of Conformity

This declaration is to declare that the products that are shown on this 

document conform with the Essential Health and Safety Requirements 

(EHSRs) of the European Machinery Directive (2006/42/EC), the 

relevant requirements of the Low Voltage Directive (2014/35/EU). 

These products also conform to 

EN 1

4119, EN ISO 13849-1, 

EN ISO 13849-2, EN 60204-1.

 Table 3 - Range Settings

Range Switch Setting

Time Delay

(Short Range) [s]

Time Delay

(Long Range) [s]

5

0.3…3

30…300

6

3…30

300…3000

7

30…300

 Table 4 - Time Settings

Time Switch Setting

Delay Adjustment

1

10%

2

20%

3

30%

4

40%

5

50%

6

60%

7

70%

8

80%

9

90%

10

100%

IMPORTANT

Do not dismantle the unit.

Содержание Prosafe 440T-MSTUEx

Страница 1: ... of the range switch To configure power the unit OFF Set the range switch to zero and the time switch to either 1 for short range timing or 10 for long range timing Apply power and adjust the time and range switches as necessary Due to intended operation of this unit only on delay range settings 5 6 and 7 can be used After adjusting the switches cycle the power to the unit to store the settings Se...

Страница 2: ... 40 A 1 N O 20 A 440T MSTUE30 2 N O 20 A 1 N C 20 A 440T MSTUE33 Dual Key Out Panel Mounted 24V DC 3 N O 40 A 1 N O 20 A 440T MDTUE10 2 N O 20 A 1 N C 20 A 440T MDTUE11 110V AC 3 N O 40 A 1 N O 20 A 440T MDTUE20 2 N O 20 A 1 N C 20 A 440T MDTUE22 230V AC 3 N O 40 A 1 N O 20 A 440T MDTUE30 2 N O 20 A 1 N C 20 A 440T MDTUE33 5 0 2 70 2 75 70 2 75 130 5 12 206 8 11 118 4 64 8 0 31 x 4 5 0 18 Ø 98 3 8...

Страница 3: ...if apparent Clean out any accumulation of fine dirt and so on Lubricate code barrel assembly with light oil or spray for example WD 40 or alternative product suitable for application Assessment of the operating environment can require the unit to be lubricated more frequently Reinstate the power and check for correct operation Repair If there is any malfunction or damage do not attempt to repair i...

Страница 4: ...on com global support get support now page Direct Dial Codes Find the Direct Dial Code for your product Use the code to route your call directly to a technical support engineer http www rockwellautomation com global support direct dial page Literature Library Installation Instructions Manuals Brochures and Technical Data http www rockwellautomation com global literature library overview page Produ...

Отзывы: