12
Getting Started with ProcessLogix R300.1
Publication 1757-QS030A-US-P - March 2000
Configuring analog input modules
To configure an analog input module:
Double-click on the IOM with the lowest number after it (for example,
IOM32). This will bring up the window for the 6-channel isolated analog
input module (1756-IF6I).
On the IOM Configuration window that is displayed, select the Main tab and
enter the following parameters:
Select the Channel Configuration tab and enter the following parameters for
all channels:
TIP
IOM32 is an example of the automatic module numbering
convention. We will provide you with an example module
number as we show you how to configure all the I/O
modules. The module numbers you see in your application
may vary.
in this field:
enter:
Module Name
LabAI
IOM Slot Number
the slot number containing this module
(remember that chassis numbering begins
with 0)
Remote I/O Chassis Mac Address
0
CNI Slot Number
0
in this field:
select:
Input Range
0V to 10V
Notch Filter
60Hz