ProcessLogix Hardware
23
Publication 1757-5.1 - August 1999
Specifications
Parameter
Operative and Storage Limits
Transportation Band
Ambient Temp Range
0 to +60°C no fans
-40 to 85°C
Temp. Rate of Change
≤
1°C/min.
≤
5°C/min.
Relative Humidity
(non-condensing)
5 to 95%
5 to 95%
Vibration (3 axes)
Frequency
Acceleration
Displacement
10 to 60 Hz
0.5 g max.
0.1 inches
10 to 60 Hz
1 g max.
0.1 inches
Mechanical Shock
Acceleration
Duration
5 g max.
30 ms max.
20 g max.
30 ms max.
Barometric Pressure
Altitude
-300 to +3000 m
Any
Corrosives
G2 std, G3 option (ISA S71.04)
G3
Module Power Requirements
+5 VDC +/- 5% @ 1.5 A
+3.3 VDC +/- 5% @ 1.0 A
Module Battery Backup Time
Lithium Battery (standard,
built in)
Battery Extension Module
(1757-BEM)
144 hours (non-rechargeable,
replaceable) - 6 days
120 hours (rechargeable) - 5 days
Lithium battery is
disconnected during
shipment.
Removal/Insertion under
power (RIUP)
NOT PERMITTED when
equipment is installed in a Class I,
Division 2, Hazardous (Classified)
Location.
PERMITTED when equipment is
installed in ordinary, non-hazardous,
locations (I/O modules reload
automatically)
CE Conformity (Europe)
89/336/EEC, EMC Directive
EN 50081-2, Emissions, Industrial
EN 50082-2, Immunity, Industrial
N/A
Agency Certifications
When product is marked:
marked for all applicable directives
Class I Div 2 Hazardous
(1)
(1)
CSA certification - Class I, Division 2, Group A,B,C,D or nonhazardous locations
or
Allen-Bradley Automation