ProcessLogix Hardware

13

Publication 1757-5.1 - August 1999

Setting up and Configuring the Server

To use the server (cat. no. 1757-PLXC) in your ProcessLogix system, you must:

connect server hardware

start and log in to the server

verify RSLinx

 communication software configuration and the ControlNet 

server address

verify Ethernet

 adapter and TCP/IP address

Connect Server Hardware

1.

To connect the server hardware, refer to the Dell PC startup documentation 
that accompanied the server.

2.

To install the 9904-KTCX15B card in your server, refer to the 9904-KTCX15B 
installation instructions that accompanied your card.

3.

Once you have connected the hardware, apply power to the server, and 
ensure that it operates correctly.

Start and Log in to the Server

1.

Apply power to the server (if you have not done so already).

2.

At the login screen, type the following:

Verify RSLInx Communication Software Configuration

To communicate with ControlNet devices, your server must have:

RSLinx communication software properly configured

an operating KTC driver

After you have successfully logged on to your server for the first time, make sure 
that RSLinx communication software is properly configured, and your server has a 
valid address for communication with ControlNet devices. Each ControlNet device 

in this field

enter

User Name

administrator

Password

password

Allen-Bradley Automation

Содержание ProcessLogix 1757-PLX52

Страница 1: ...o understand installation requirements TIP Fo For installation information and specifications for the Redundancy Module refer to publication 1757 5 15 shipped with the 1757 SRM Redundancy Module For specifications for each module in your system refer to the documentation that was shipped with the module s IMPORTANT The 1757 PLX52 Process Controller module is supplied with only the boot code instal...

Страница 2: ...in this publication Allen Bradley publication SGI 1 1 Safety Guidelines for the Application Installation and Maintenance of Solid State Control available from your local Allen Bradley office describes some important differences between solid state equipment and electromechanical devices that should be taken into consideration when applying products such as those described in this publication Repro...

Страница 3: ...t 2 Industrial Environment EN 5001082 2 EMC Generic Immunity Standard Part 2 Industrial Environment This product is intended for use in an industrial environment Low Voltage Directive This product is tested to meet Council Directive 73 23 EEC Low Voltage by applying the safety requirements of EN 61131 2 Programmable Controllers Part 2 Equipment Requirements and Tests For specific information requi...

Страница 4: ...Some ProcessLogix modules e g I O and communications modules as well as the 1757 PLX52 Process Controller module have been designed to permit removal and insertion under power RIUP without damaging the module or interrupting backplane communications Any time electrical connections are made or broken there is a potential for arcing or sparking Do not remove or insert any modules while they are stil...

Страница 5: ...phillips screwdriver torque screwdriver needle nose pliers crimping tool Set the Line Voltage Input Jumper Use needle nose pliers to set the jumper to the correct position TIP Ensure that you have properly calculated the backplane requirements for the power supply you are installing IMPORTANT The HI and LOW positions are marked on the power supply s circuit board for this power supply set jumper t...

Страница 6: ...nd power supply to the ground bus Stationary Nut To ground bus Equipment grounding conductor ground lug with 2 1 mm2 14 AWG wire safety ground from chassis to ground bus Equipment grounding conductor ground lug with 2 1 mm2 14 AWG wire safety ground from power supply Nut with captive stare washer 30188 M Safety gound terminal stud Wiring terminal block Nut with captive star washer Safety ground te...

Страница 7: ...ix Hardware 7 Publication 1757 5 1 August 1999 IMPORTANT We recommend using a ground bus because it reduces the electrical resistance at the connection 20231a M Earth Ground Keep wire lengths as short as possible ...

Страница 8: ...the top of the power supply 2 Apply power by toggling the switch on the front of the power supply from OFF to ON ATTENTION Turn off power lines before connecting power Failure to do so could cause injury to personnel and or damage to equipment IMPORTANT Make sure you mount the chassis and complete work on the panel before you remove the protective label The label protects the power supply from met...

Страница 9: ...r 7 If the indicator turns on verify that the system module loads are within the output rating of the power supply and re install the power supply in the chassis 8 If the LED turns off return the power supply to your local Rockwell Automation distributor Installing the ControlNet Communications Module Install the 1756 CNB module for ControlNet communications into slot 0 of the chassis 1 Align the ...

Страница 10: ... to conserve power To install the battery 1 Open the front door of the 1752 PLX module 2 Locate the battery connector a small white plug at the end of a pair of red and black twisted wires TIP The module is fully installed when it is flush with the other installed modules To remove the module push down on the locking clips at the top and bottom of each module Slide the module out of the chassis AT...

Страница 11: ...rong male plug in the battery compartment 4 Slide the 1757 PLX52 module into the chassis into the first slot at the far left of the chassis 5 Insert the end of the battery away from the lead wire into the recessed area in the module Make sure the black retaining tab located next to the battery lead terminal clicks and secures the battery in its holder Battery Holder Battery Lead Terminal Battery h...

Страница 12: ... chassis 2 Slide the module into the chassis Make sure the module properly connects to the chassis backplane TIP F For information on installing I O modules refer to the documentation that was shipped with the module TIP The module is fully installed when it is flush with the other installed modules To remove the module push down on the locking clips at the top and bottom of each module Slide the ...

Страница 13: ...on instructions that accompanied your card 3 Once you have connected the hardware apply power to the server and ensure that it operates correctly Start and Log in to the Server 1 Apply power to the server if you have not done so already 2 At the login screen type the following Verify RSLInx Communication Software Configuration To communicate with ControlNet devices your server must have RSLinx com...

Страница 14: ...RSLinx RSLinx opens in about ten seconds 2 Select Communications Configure Drivers Verify RSLinx communication software configuration Once you have started RSLinx you can verify that it has been configured correctly When you select Communications Configure Drivers in RSLinx you see a screen that looks like this one if you see this in the Configured Drivers window then AB_KTC 1 CNET MAC Addr RUNNIN...

Страница 15: ...n the Configured Drivers window AB_KTC 1 CNET MAC Addr RUNNING You see the Configure Allen Bradley KTC X Device screen 1 Verify that the ControlNet address is configured correctly In the MAC ID field check that the MAC ID is equal to 20 2 Close the Configure Drivers screen 3 To close RSLinx select File Exit TIP The ControlNet address is called the MAC ID on some screens ...

Страница 16: ...thernet adapter 1 In your Microsoft Windows NT desktop select Start Settings Control Panel 2 Double click on the Network icon You see the Network screen 3 Click the Adapters tab You see the Network Adapters screen IMPORTANT If your server and remote stations do not have Ethernet cards installed you can use the Microsoft loopback adapter provided with the NT operating system The loopback adapter is...

Страница 17: ...on accompanying the Ethernet card or loopback adapter for more information Verify the TCP IP address Verify the TCP IP address only if your system will communicate with remote stations Otherwise skip this section 1 From the Network menu click on the Protocols tab 2 In the Network Protocols field double click on TCP IP Protocol 3 On the TCP IP Properties screen that appears select the Ethernet adap...

Страница 18: ...pending on changes you made to your configuration you may need to reboot your system Shut down all applications before rebooting the system 5 To close the TCP IP properties screen click on Cancel 6 To close the network program click Cancel 7 To close the Windows Control Panel select File Close Installing ControlNet Cabling To install the ControlNet cabling for ControlNet communications you will ne...

Страница 19: ...or on one side of each dropline 2 Connect each dropline to a 1786 BNCP cable 3 Connect the bottom of one dropline to the 1756 CNB module 4 Connect the bottom of the other dropline to the 9904 KTCX15B card installed in the server 20954 M ProcessLogix controller ProcessLogix server ControlNet link 1756 CNB module ...

Страница 20: ...s CSA logo is a registered trademark of the Canadian Standards Association Due to the modular nature of a programmable control system the product with the highest temperature rating determines the overall temperature code rating of a programmable control system in a Class I Division 2 location The temperature code rating is marked on the product label as shown Explosion hazard Substitution of comp...

Страница 21: ...ProcessLogix Hardware 21 Publication 1757 5 1 August 1999 Approbation d utilisation dans des environnements dangereux par la ...

Страница 22: ...ux AVERTISSEMENT Le sigle CSA est une marque déposée de la Canadian Standards Association De par la nature modulaire des systèmes de commande programmables le produit ayant le code de température le plus élevé détermine le code de température global du système dans un environnement de Classe I Division 2 Le code de température est indiqué sur l étiquette produit Risque d explosion La substitution ...

Страница 23: ... 1 5 A 3 3 VDC 5 1 0 A Module Battery Backup Time Lithium Battery standard built in Battery Extension Module 1757 BEM 144 hours non rechargeable replaceable 6 days 120 hours rechargeable 5 days Lithium battery is disconnected during shipment Removal Insertion under power RIUP NOT PERMITTED when equipment is installed in a Class I Division 2 Hazardous Classified Location PERMITTED when equipment is...

Страница 24: ...Publication 1757 5 1 August 1999 PN 957208 55 Supersedes Publication 1757 5 1 May 1999 1999 Rockwell International Corporation Printed in the U S A Notes ...

Отзывы: