Publication 1757-RM810A-EN-P - May 2002
3-28
Functional Blocks
RS (Reset dominant SR-FLIP-FLOP)
RTRIG (Rising edge Trigger)
SEL (Binary Selection)
Description
Provides a bistable Reset Dominant flip-flop as defined in the IEC DIS 1131-3 standard.
Function
Specifies the output (Q) of the flip-flop as a function of the input S (Set), the input R (Reset), and the last state of Q.
Truth Table
S
0 (OFF)
0 (OFF)
1 (ON)
1 (ON)
R
0 (OFF)
1 (ON)
0 (OFF)
1 (ON)
Q
No Change
0 (OFF)
1 (ON)
0 (OFF)
Inputs
S and R = Boolean value
Outputs
Q = Boolean value controlled by the status of the input signals.
Parameters
ORDERINCM
Q
R
S
Description
Rising-edge Trigger sets the output (OUT) to ON following the OFF-to-ON transition of the input (IN) and stays at ON
until the next execution cycle, at which time it returns to OFF.
Function
Provides rising edge change detection, thereby turning the output ON if an OFF-to-ON transition is detected.
Inputs
IN = Boolean value
Outputs
OUT = Boolean value
Parameters
IN
ORDERINCM
OUT
Description
Provides a 3-input selector function, meaning it selects 1 of 2 inputs (IN [1] or IN [2]) depending on the separate
input G.
Function
Sets the actual output (OUT) equal to the value of 1 of 2 inputs (IN [1] or IN [2]), depending on the value of a separate
input (G).
Truth Table
IN [1]
IN [1]
IN [1]
IN [2]
IN [2]
IN [2]
G
OFF
ON
OUT
IN [1]
IN [2]
Inputs
IN [1..2] =Boolean value
G = Boolean value
Outputs
OUT =Boolean value depending on the values of IN [1] and IN [2].
Parameters
G
IN [0..2]
Содержание ProcessLogix 1756-IA16
Страница 1: ...ProcessLogix Function Blocks 1757 Series Reference Manual Spare Allen Bradley Parts...
Страница 2: ......
Страница 40: ...Publication 1757 RM810A EN P May 2002 2 20 Physical Equipment Blocks...
Страница 116: ...Publication 1757 RM810A EN P May 2002 3 76 Functional Blocks...
Страница 119: ...Spare Allen Bradley Parts...