Publication 1757-RM810A-EN-P - May 2002
Functional Blocks
3-5
DEADTIME
Description
Provides calculated output (PV) in which value changes may be delayed from the time that the corresponding change
occurred in the P1 input. The delay time can be fixed, or it can vary as the inverse of another input (P2).
Function
Applies a fixed or variable delay to a process input value
Inputs
Requires an input value (P1); a second input (P2) is optional.
P1 and P2 must be fetched from other function blocks
Outputs
Produces the following output:
PV and it’s status, PVSTS and PVSTSFL
Operators and
Functions
Table 3.A on page 3-4 lists the expression operators and functions supported by this block for reference.
Delay Table
Is used to accomplish the desired delays in the input (P1). P1 values are stored and shifted through the table at a rate
that is calculated to produce the desired Deadtime. The table-shift rate is derived from the following information:
•
The sample rate of the P1 value (TS). This is the execution rate of the function block.
•
The delay time (DELAYTIME). If fixed delay is selected, user specifies the delay; if variable delay is selected, the
delay is derived from P2.
•
The number of entries to use in the delay table (NUMLOC). The table has a maximum of 60 entries, but the user
may request to use fewer than that (by sorting to NUMLOC).
Delay Type
Two types of delay are supported:
•
Fixed Delay
•
Variable Delay
Parameters
C1
C2
CPV
CUTOFF.LM
D1
D2
DELAYTABLE [1..60]
DELAYTIME
DELAYTYPE
DESC
DPV
INITREQ
NUMLOC
ORDERINCM
P1
P1STS
P2
P2STS
PV
PVFORMAT
PVSTS
PVSTSFL.BAD
PVSTSFL.MAN
PVSTSFL.NORM
PVSTSFL.UNCER
PVVALSTS
Содержание ProcessLogix 1756-IA16
Страница 1: ...ProcessLogix Function Blocks 1757 Series Reference Manual Spare Allen Bradley Parts...
Страница 2: ......
Страница 40: ...Publication 1757 RM810A EN P May 2002 2 20 Physical Equipment Blocks...
Страница 116: ...Publication 1757 RM810A EN P May 2002 3 76 Functional Blocks...
Страница 119: ...Spare Allen Bradley Parts...