3-26
Programming and Parameters
Terminal Block Group
(continued)
T086 [Analog Out2 High]
Related Parameter(s):
Scales the Maximum Output Value for the A065 [Analog Out Sel] source setting.
Examples:
Values
Default:
100%
Min/Max:
0/800%
Display:
1%
T086 Setting
T085 Setting
T085 Max. Output Value
50%
1 “OutCurr 0-10”
5V for 200% Drive Rated Output Current
90%
11 “OutPowr 0-20”
18mA for 200% Drive Rated Power
T087 [Anlg Out2 Setpt]
Related Parameter(s):
Sets direct parameter control over the analog output. If enabled, this sets the percent value of analog
output.
Values
Default:
0.0%
Min/Max:
0.0/100.0%
Display:
0.1%
T088 [Anlg Loss Delay]
,
,
Sets the length of time after power-up during which the drive will not detect an analog signal loss. The
drive response to an analog signal loss is set in
or
[Analog In x Loss].
Values
Default:
0.0 Secs
Min/Max:
0.0/20.0 Secs
Display:
0.1 Secs