18
Rockwell Automation Publication 520-UM002B-EN-E - December 2017
Chapter 1
Installation/Wiring
Input Power Conditioning
The drive is suitable for direct connection to input power within the rated
voltage of the drive (see
Technical Specifications on page 135
). Listed in the
table below are certain input power conditions which
may cause component damage or reduction in product life. If any of these
conditions exist, install one of the devices listed under the heading Corrective
Action on the line side of the drive.
General Grounding
Requirements
The drive Safety Ground -
(PE) must be connected to system ground. Ground
impedance must conform to the requirements of national and local industrial
safety regulations and/or electrical codes. The integrity of all ground connections
should be periodically checked.
Typical Grounding
IMPORTANT
Only one device per branch circuit is required. It should be mounted closest to
the branch and sized to handle the total current of the branch circuit.
Input Power Conditions
Input Power Condition
Corrective Action
Low Line Impedance (less than 1% line reactance)
•
Install Line Reactor
(2)
•
or Isolation Transformer
(2) See
for accessory ordering information.
Greater than 120 kVA supply transformer
Line has power factor correction capacitors
•
Install Line Reactor
(2)
•
or Isolation Transformer
Line has frequent power interruptions
Line has intermittent noise spikes in excess of 6000V (lightning)
Phase to ground voltage exceeds 125% of normal line to line voltage
•
Remove MOV jumper to ground.
•
or Install Isolation Transformer with
grounded secondary if necessary.
Ungrounded distribution system
240V open delta configuration (stinger leg)
(1)
(1) For drives applied on an open delta with a middle phase grounded neutral system, the phase opposite the phase that is tapped in
the middle to the neutral or earth is referred to as the “stinger leg,” “high leg,” “red leg,” etc. This leg should be identified throughout
the system with red or orange tape on the wire at each connection point. The stinger leg should be connected to the center Phase B
on the reactor. See
Bulletin 1321-3R Series Line Reactors on page 147
for specific line reactor part numbers.
•
Install Line Reactor
(2)
SHLD
U/T1
V/T2
W/T3
R/L1
S/L2
T/L3
Содержание PowerFlex 527
Страница 1: ...PowerFlex 527 Adjustable Frequency AC Drive Catalog Number 25C User Manual Original Instructions...
Страница 4: ...4 Rockwell Automation Publication520 UM002B EN E December 2017 Summary of Changes Notes...
Страница 8: ...8 Rockwell Automation Publication 520 UM002B EN E December 2017 Table of Contents Notes...
Страница 102: ...102 Rockwell Automation Publication520 UM002B EN E December 2017 Chapter 5 Hardwired Control of Safe Torque Off Notes...
Страница 162: ...162 Rockwell Automation Publication520 UM002B EN E December 2017 Appendix B Accessories and Dimensions Notes...
Страница 173: ...Rockwell Automation Publication520 UM002B EN E December 2017 173 Notes...
Страница 174: ...174 Rockwell Automation Publication 520 UM002B EN E December 2017 Notes...
Страница 175: ......