Allen-Bradley POINT I/O series Скачать руководство пользователя страница 9

POINT I/O 2 and 4 Relay Output Modules     

9

Publication 1734-IN055H-EN-E - August 2016

Install the Module

The module can be installed before or after base installation. Make sure that the mounting 
base is correctly keyed before installing the module into the mounting base. In addition, 
make sure the mounting base locking screw is positioned horizontal in reference to 
the base.

1. Using a bladed screwdriver to rotate the keyswitch on the mounting base 

clockwise until the number required for the type of module being installed aligns 
with the notch in the base.

2. Make certain the DIN rail locking screw is in the horizontal position.

 

You cannot insert the module if the locking mechanism is unlocked.

WARNING: 

When you insert or remove the module while backplane power is 

on, an electrical arc can occur. This could cause an explosion in hazardous 
location installations.

Be sure that power is removed or the area is nonhazardous before proceeding. 
Repeated electrical arcing causes excessive wear to contacts on both the 
module and its mating connector. Worn contacts may create electrical 
resistance that can affect module operation.

Содержание POINT I/O series

Страница 1: ...onment and Enclosure 3 Preventing Electrostatic Discharge 3 North American Hazardous Location Approval 4 European Hazardous Location Approval 5 About the Module 6 Mount the I O Base 8 Install the Modu...

Страница 2: ...installation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams No patent liability is assumed by Rockwell Automation Inc with respect...

Страница 3: ...or minimize the spread of flame complying with a flame spread rating of 5VA or be approved for the application if nonmetallic The interior of the enclosure must be accessible only by the use of a too...

Страница 4: ...ts dans le syst me sont sujettes inspection par les autorit s locales qualifi es au moment de l installation EXPLOSION HAZARD Do not disconnect equipment unless power has been removed or the area is k...

Страница 5: ...an environment of not more than Pollution Degree 2 as defined in IEC 60664 1 when applied in Zone 2 environments The enclosure must utilize a tool removable cover or door WARNING This equipment shall...

Страница 6: ...les The wiring base assembly consists of a mounting base 1734 MB and removable terminal block 1734 RTB or 1734 RTBS and 1734 TOP or 1734 TOPS one piece terminal base Modules Mounted on Removable Termi...

Страница 7: ...4 TOPS One piece Terminal Base Description Description 1 Module locking mechanism 5 Interlocking side pieces 2 Slide in writable label 6 Mechanical keying 3 Handle 7 DIN rail locking screw orange 4 17...

Страница 8: ...g side pieces to engage the adjacent module or adapter 3 Press firmly to seat the mounting base on the DIN rail The mounting base snaps into place ATTENTION This product is grounded through the DIN ra...

Страница 9: ...the number required for the type of module being installed aligns with the notch in the base 2 Make certain the DIN rail locking screw is in the horizontal position You cannot insert the module if th...

Страница 10: ...2016 3 Insert the module straight down into the mounting base and press to secure The module locks into place Turn the keyswitch to align the number with the notch Notch position 3 is shown Make sure...

Страница 11: ...utput Modules 11 Publication 1734 IN055H EN E August 2016 Turn the keyswitch to align the number with the notch Notch position 1 is shown Make sure the DIN rail locking screw is in the horizontal posi...

Страница 12: ...e wiring base 2 Rotate the terminal block into the wiring base until it locks itself in place 3 If an I O module is installed snap the RTB handle into place on the module WARNING When you connect or d...

Страница 13: ...mm diameter blade into the opening at approximately 73 blade surface is parallel with top surface of the opening and push up gently WARNING For 1734 TOPS and 1734 TOP3S to latch and un latch the wire...

Страница 14: ...right 6 Use a small bladed screwdriver to rotate the orange base locking screw to a vertical position This releases the locking mechanism 7 Lift straight up to remove Communicate with Your Module I O...

Страница 15: ...ure that power is removed or the area is nonhazardous before proceeding Relay Output Module Status Network Status 1734 OW4 NODE 0 1 2 3 Relay Output Module Status Network Status 1734 OW2 0 1 NODE Modu...

Страница 16: ...Powered by External Power Bus Load power must be provided by an external power source for the 1734 OW4 The 1734 OW4 cannot be powered from the internal power bus Channel Output Channel Output 0A 0 2A...

Страница 17: ...l The slightest variation in relay switching time may cause one relay to momentarily switch the total load current ATTENTION Make sure that all relay wiring is properly connected before applying any p...

Страница 18: ...4 5 6 7 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 0 1 2 3 4 5 6 7 PDN IB2 IB4 IV2 IV4 FPD OW2 AC power bus C V L2 N L1 45187 OW2 OW2 0 1 0 1 0 1 0...

Страница 19: ...diagram and table for information on how to interpret the status indicators Relay Output Module Status Network Status 1734 OW4 NODE 0 1 2 3 Relay Output Module Status Network Status 1734 OW2 0 1 NODE...

Страница 20: ...us Off Device is not online Device has not completed dup_MAC id test Device not powered check module status indicator Flashing green Device is online but has no connections in the established state Gr...

Страница 21: ...ximum rating at voltages between the maximum design value and 120V the maximum make and break ratings are to be obtained by dividing the volt amperes rating by the application voltage For voltages bel...

Страница 22: ...ckaged Damp Heat 5 95 noncondensing Vibration IEC 60068 2 6 Test Fc Operating 5 g 10 500 Hz Shock operating IEC 60068 2 27 Test Ea Unpackaged Shock 30 g Shock nonoperating IEC 60068 2 27 Test Ea Unpac...

Страница 23: ...opean Union 2014 35 EU LVD compliant with EN 61131 2 Programmable Controllers Clause 11 Ex European Union 2014 34 EU ATEX Directive compliant with EN 60079 15 2010 Potentially Explosive Atmospheres Pr...

Страница 24: ...s to be returned follow these procedures Documentation Feedback Your comments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete th...