Publication 1734-UM003A-EN-P - August 2000
6-2
Troubleshooting with the Indicators
Indication
Probable Cause
Network Status
Off
Device is not on-line
- Device has not completed dup_MAC_id test.
- Device not powered - check module status indicator
Flashing Green
Device is on-line but has no connections in the established
state.
Green
Device on-line and has connections in the established state.
Flashing Red
One or more I/O connections in timed-out state
Red
Critical link failure - failed communication device. Device
detected error that prevents it communicating on the
network.
Flashing
Red/Green
Communication faulted device - the device has detected a
network access error and is in communication faulted state.
Device has received and accepted an Identify
Communication Faulted Request - long protocol message.
Indication
Probable Cause
Input Status
Off
Input inactive
Yellow
Input is active and under control
Indication
Probable Cause
Output Status
Off
Output inactive
Yellow
Output is active and under control
Flashing Yellow
Output is toggling
Flashing Red
Output is faulted (open, short or no output power)
Flashing
Red/Yellow
Output is toggling and faulted (possibly open)