     PanelView Component HMI Terminals

Publication 2711C-IN001H-EN-P - July 2014

North American Hazardous Location Approval - For 2711C-T4T only

  

The following information applies when 
operating this equipment in hazardous 
locations:

Informations sur l’utilisation de cet équipement 
en environnements dangereux:

Products marked "CL I, DIV 2, GP A, B, C, D" are suitable for 
use in Class I Division 2 Groups A, B, C, D, Hazardous 
Locations and nonhazardous locations only. Each product is 
supplied with markings on the rating nameplate indicating 
the hazardous location temperature code. When combining 
products within a system, the most adverse temperature 
code (lowest "T" number) may be used to help determine the 
overall temperature code of the system. Combinations of 
equipment in your system are subject to investigation by the 
local Authority Having Jurisdiction at the time of installation.

Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne 
conviennent qu'à une utilisation en environnements de Classe 
I Division 2 Groupes A, B, C, D dangereux et non dangereux. 
Chaque produit est livré avec des marquages sur sa plaque 
d'identification qui indiquent le code de température pour les 
environnements dangereux. Lorsque plusieurs produits sont 
combinés dans un système, le code de température le plus 
défavorable (code de température le plus faible) peut être 
utilisé pour déterminer le code de température global du 
système. Les combinaisons d'équipements dans le système 
sont sujettes à inspection par les autorités locales qualifiées 
au moment de l'installation.

EXPLOSION HAZARD

• Do not disconnect equipment 

unless power has been removed 
or the area is known to be 
nonhazardous. 

• Do not disconnect connections 

to this equipment unless power 
has been removed or the area is 
known to be nonhazardous. 
Secure any external 
connections that mate to this 
equipment by using screws, 
sliding latches, threaded 
connectors, or other means 
provided with this product.

• Substitution of components may 

impair suitability for Class I, 
Division 2.

• If this product contains 

batteries, they must only be 
changed in an area known to be 
nonhazardous.

RISQUE D’EXPLOSION

• Couper le courant ou s’assurer 

que l’environnement est classé 
non dangereux avant de 
débrancher l'équipement.

• Couper le courant ou s'assurer 

que l’environnement est classé 
non dangereux avant de 
débrancher les connecteurs. 
Fixer tous les connecteurs 
externes reliés à cet équipement 
à l'aide de vis, loquets 
coulissants, connecteurs filetés 
ou autres moyens fournis avec ce 
produit.

• La substitution de composants 

peut rendre cet équipement 
inadapté à une utilisation en 
environnement de Classe I, 
Division 2.

• S’assurer que l’environnement 

est classé non dangereux avant 
de changer les piles.

IMPORTANT

Only the 2711C-T4T catalog is UL Listed for Class I, Division 2 Group A,B,C,D Hazardous 
Locations, certified for U.S. and Canada.

Содержание PanelView C1000

Страница 1: ...es not provide information on how to configure or run applications on the following devices 2711C F2M 2711C K2M 2711C T3M 2711C K3M 2711C T6M 2711C T4T 2711C T6C 2711C T6T 2711C T10C Topic Page Enviro...

Страница 2: ...tallation Rockwell Automation Inc cannot assume responsibility or liability for actual use based on the examples and diagrams No patent liability is assumed by Rockwell Automation Inc with respect to...

Страница 3: ...specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts The enclosure must have suitable flame retardan...

Страница 4: ...faible peut tre utilis pour d terminer le code de temp rature global du syst me Les combinaisons d quipements dans le syst me sont sujettes inspection par les autorit s locales qualifi es au moment d...

Страница 5: ...ns against leaks and maintain IP enclosure type requirements ATTENTION This product is intended to be mounted to a well grounded mounting surface such as a metal panel Additional grounding connections...

Страница 6: ...lay without having to download first PanelView Component C200 and C300 Terminals Cat No Model Operator Input Size Display Type 2711C F2M C200 Function keys 2 in Monochrome 2711C K2M Numeric and functi...

Страница 7: ...485 port 6 USB host Item Description Item Description 1 Touch display function keys 7 24V DC power input 2 Power status LED 1 1 The Power Status LED is red when in screen saver or dimmer mode and gree...

Страница 8: ...C600 2711C T6M 2711 T6C Series C or later 2711C T6T Series A or later Item Description Item Description 1 Touch display 7 USB device port 2 24V DC power input 8 Diagnostic status indicator 3 10 100 MB...

Страница 9: ...ines Supporting panels must be at least 16 gauge to provide proper sealing against water and dust and to provide proper support The panel surface must be flat and free of imperfections to maintain an...

Страница 10: ...52 0 04 99 0 1 0 3 90 0 04 C200 and C300 Keypad C400 Touchscreen and function keys 99 0 1 0 3 90 0 04 119 0 1 0 4 69 0 04 C600 Touch 135 0 1 0 5 31 0 04 189 0 1 0 7 44 0 04 C1000 Touch 231 0 1 0 9 09...

Страница 11: ...he enclosure and the gasket is fully compressed You will hear a series of clicks as the clamps self adjust to the panel thickness IMPORTANT The terminal temperature must be greater than 0 C 32 F durin...

Страница 12: ...de each lever until the short flat side of the lever touches the surface of the panel 3 When both levers are in place slide each lever an additional notch or two until you hear a click ATTENTION Follo...

Страница 13: ...2711C T6M T6C Series C or later 2711C T6T Series A or later only terminal release the mounting lever by rotating it in the direction indicated slide it to the bottom of the mounting slot and remove it...

Страница 14: ...elease each panel clamp from its locked position Do this as soon as possible after the removing the terminal from the panel Follow these steps to unlock each panel clamp 1 Insert the tip of a flat bla...

Страница 15: ...teps to mount the terminal in a panel ATTENTION Follow these guidelines when mounting the terminal in a panel Disconnect all electrical power from the panel before making the panel cutout Make sure th...

Страница 16: ...el cutout 4 Insert all mounting levers into the mounting slots on the terminal Slide each lever until the short flat side of lever touches the surface of the panel 5 When all levers are in place slide...

Страница 17: ...gs for Alignment Lever Position Panel Thickness Range Typical Gauge 1 1 52 2 01 mm 0 060 0 079 in 16 2 2 03 2 64 mm 0 08 0 104 in 14 3 2 67 3 15 mm 0 105 0 124 in 12 4 3 17 3 66 mm 0 125 0 144 in 10 5...

Страница 18: ...nt C200 and C300 Dimensions PanelView Component Height Approx Width Approx Overall Depth Approx Mounted Depth Approx a b c d C200 Keypad C300 Keypad 119 mm 4 69 in 139 mm 5 47 in 55 mm 2 15 in 49 mm 1...

Страница 19: ...anelView Component HMI Terminals 19 Publication 2711C IN001H EN P July 2014 PanelView Component C400 Touch Terminals PanelView Component C600 Touch Terminals a b c d 45850 PanelView C600 a b c d 44884...

Страница 20: ...same ground system connect to the USB peripheral through a galvanically isolated hub PanelView Component C600 C1000 and C400 Dimensions PanelView Component Height Approx Width Approx Overall Depth App...

Страница 21: ...not use the USB port in hazardous locations ATTENTION Use a Class 2 Safety Extra low Voltage SELV or Protective Extra low Voltage PELV power supply as required by local wiring codes for your installat...

Страница 22: ...ports SELV or PELV power supply Other equipment can share this power supply with the PanelView Component device provided that no ground loops are created A PELV power source internally connects the ne...

Страница 23: ...t devices connect to a 24V DC power source The table shows the power ratings for each device The internal nonisolated power supply is protected against reverse polarity of the DC and DC connections Po...

Страница 24: ...or disconnect wiring while the power is on an electrical arc can occur This could cause an explosion in hazardous location installations Be sure that power is removed or the area is nonhazardous befor...

Страница 25: ...ION The functional earth connection to ground is mandatory This connection is required for noise immunity reliability and Electromagnetic Compliance EMC with the European Union EU EMC directive for CE...

Страница 26: ...r This value is compatible with RS422 and RS485 electrical specifications Additional termination on the PanelView Component end of communication cables is not required Troubleshooting If your terminal...

Страница 27: ...g the life of the product The battery provides battery backup for the real time clock It is not used for application backup or retention Fault Indicator States During Startup Fault Red Indicator State...

Страница 28: ...y in a fire or incinerator Dispose of used batteries in accordance with local regulations WARNING When you connect or disconnect the battery an electrical arc can occur This could cause an explosion i...

Страница 29: ...e battery cover and replace the battery Battery Cover Battery 44888 This equipment is sensitive to electrostatic discharge ESD Follow ESD prevention guidelines when handling this equipment C600 C1000...

Страница 30: ...matrix LCD Display size 2 in 3 in 4 in 5 7 in 10 4 in Display area 49 x 14 mm 1 93 x 0 55 in 67 x 33 mm 2 64 x 1 30 in 95 04 x 53 86 mm 3 74 X 2 12 in 115 x 86 mm 4 53 x 3 39 in 211 x 158 mm 8 31 x 6...

Страница 31: ...time tested on a representative sample Wire size Single Wire Gauge 0 33 2 08 mm2 22 14 AWG Dual wire Gauge 0 33 1 31 mm2 22 16 AWG Earth wire 2 08 3 31 mm2 14 12 AWG Wire type Solid or stranded coppe...

Страница 32: ...1 kHz sine wave 80 AM from 1400 2000 MHz 1V m with 1 kHz sine wave 80 AM from 2000 2700 MHz EFT B Immunity IEC 61000 4 4 2 kV 5 kHz on power ports 1 kV 5 kHz on communication ports Surge Transient Imm...

Страница 33: ...on distributor or sales representative EAC Russian Customs Union TR CU 020 2011 EMC Technical Regulation RCM Australian Radiocommunications Act compliant with AS NZS CISPR 11 Industrial Emissions KC K...

Страница 34: ...34 PanelView Component HMI Terminals Publication 2711C IN001H EN P July 2014 Notes...

Страница 35: ...PanelView Component HMI Terminals 35 Publication 2711C IN001H EN P July 2014 Notes...

Страница 36: ...information that s contained in this manual You can also contact a special Customer Support number for initial help in getting your product up and running New Product Satisfaction Return Rockwell Auto...

Отзывы: