PanelView Component HMI Terminals
27
Publication 2711C-IN001H-EN-P - July 2014
Interpret the LED Indicators at Startup
The C400, C600 and C1000 terminals have indicators on the back of the unit to isolate operating problems.
•
Comm indicator for communications
•
Fault indicator for hardware faults
At startup, the Fault indicator is off, except for a few brief flashes, and the Comm indicator is on. If the
indicators remain off, check the power cable. After a successful startup, both indicators are off and controlled
by the application running on the terminal.
The table shows the indicator states if the terminal stops during startup.
Battery Replacement
The C400, C600 and C1000 terminals contain a lithium battery that is intended to be replaced during the
life of the product. The battery provides battery backup for the real-time clock.
It is not used for application backup or retention.
Fault Indicator States During Startup
Fault (Red)
Indicator State
Comm (Green)
Indicator State
Description
Recommended Action
Potentially recoverable errors
Blinking
Off
Last firmware download failed.
Reload the firmware.
Blinking
Blinking
EBC boot loader firmware failed or
is missing.
Reload the firmware.
Blinking
On
Windows CE OS firmware failed or
is missing.
Reload the firmware.
Nonrecoverable or fatal errors
On
Off
Fatal hardware error.
Replace the terminal.
On
Blinking
Fatal display hardware error.
Replace the terminal.
WARNING:
Verify that power has been removed from the terminal prior to replacing the battery.
Work in a static free environment and wear a properly grounded electrostatic discharge (ESD)
wristband. Be careful when touching any of the exposed electronic components to prevent
damage from ESD.