Product Overview
1-3
Default Settings
The ENI’s RS-232 port has the following default settings:
Table 1.1 RS-232 Settings
Setting
Default
Other Options
Baud Rate
Autobaud
see table 4.7
Handshaking (hardware, software)
none
none
Data Bits
8
none
Stop Bits
1
none
Parity
none
none
Table 1.2 DF1 Settings
Setting
Default
Other Options
Duplicate Message Detection
Enable
none
Error Detection
CRC, BCC
Auto-detect when
Autobaud is true,
otherwise CRC
Embedded Response Operation
Auto-Detect, for
reception only
(1)
(1) The ENI receives NAKs and ACKs, but does not generate them.
none
DLE ACK Timeout
1 second
none
DLE NAK Receive
3 NAK retries
none
DLE ENQ for Response
3 ENQs retries
none
DF1 Node Address
Don’t Care