background image

Rockwell Automation Publication 440R-IN081B-EN-P - February 2020

3

Back EMF Monitoring Relay Module

Connect Power Supply

Power for the MSR55P standstill module safety relay depends on the 

model. The primary power supply is connected to terminals A1 and A2. 

An auxiliary (12…30V DC only) supply voltage can be connected to 

terminals A3/A4 to provide semiconductor diagnostics.
Depending on the model, the primary supply can be 24V DC, 115V 

AC, or 230V AC. When an AC supply is used, both 50 Hz and 60 Hz 

are acceptable.
When powering with 24V DC in the European Union, the DC supply 

must have a Protective Extra-Low Voltage (PELV) rating. When 

powering with 24V DC in the United States, the DC supply must have 

both a PELV rating as well as an NEC Class 2 rating. Many of our 

Bulletin 1606 power supplies are PELV and Class 2 compliant.
Power to A1/A2 is required to operate the MSR55P standstill module 

safety relay. Power to A3/A4 is only necessary if the solid-state auxiliary 

status signals (ON and ERR) are used.

Motor Winding Inputs

The motor windings are connected to terminals L1, L2, and L3. The 

connections must be made directly at the motor with no electrical 

devices (like transformers and contactors) between the motor and the 

MSR55P safety relay. 

Figure 3

 shows wiring for a single-phase, DC, and 

a three-phase motor.

Figure 2 - Motor Connections

Surge Suppressors

Because of the potentially high current surges that occur when switching 

inductive load devices, such as motor starters and solenoids, the use of 

surge suppression is required. Adding a suppression device prolongs the 

life of the relay outputs and reduces the effects of voltage transients and 

electrical noise from radiating into adjacent systems. 
Since this is a safety-related system, the surge suppression device must 

connected across the load device. The surge suppression device must not 

be connected across the MSR55P safety relay contacts. 
For outputs that use 24V DC, we recommend 1N4001 (50V reverse 

voltage) to 1N4007 (1000V reverse voltage) diodes for surge 

suppression. The diode must be connected as close as possible to the 

load coil.
For outputs that use 120V AC or 240V AC, we recommend metal oxide 

varistors.

Configuration

The configuration of MSR55P safety relays is accomplished by 

adjusting the two switches on the front face. Each switch control knob 

rotates two potentiometers. The recommended practice is to set the 

switches to the minimum setting initially, and then adjust them as 

necessary to reduce nuisance tripping while maintaining a safe 

application.

V

m

 - Monitoring Voltage

The trip voltage of the back EMF is adjusted by the 10-position V

m

 

potentiometer. When the back EMF drops below the voltage level, the 

MSR55P standstill module safety relay begins the delay timer. After the 

timer expires, the outputs are de-energized. 

Table 2

 shows the settings of 

each of the catalog numbers.

Table 2 - V

m

 

- Monitoring Voltage Settings

t

s

 - Time Delay

When the back EMF of the motor drops below the V

voltage setting, 

the standstill delay timer starts. The delay time is set by the 10-position 

t

s

 

potentiometer. During the timing cycle, the OUT indicator flashes. 

Table 3 on page 4

 shows the delay time for each setting. After the delay 

expires, the outputs are energized.

IMPORTANT

The three connections create two safety monitor channels. L1 
is common to the two channels, which are L2 and L3.

L1 L2

L3

M

K1

K2

A2

X1 X2

1

L

2

L

3

L

X3

34

44

A1

A3

1

1

3

2

3

3

2

1

4

2

ON ERR A4

54

43

53

L1 N

M

K1

K2

A2

X1 X2

1

L

2

L

3

L

X3

34

44

A1

A3

1

1

3

2

3

3

2

1

4

2

ON ERR A4

54

43

53

Single-phase and DC Motor

Three-phase

Position

440R-S35014, 440R-S35015, 

440R-S35016 [Volts]

440R-S35011, 440R-S35012, 

440R-S35013 [x10mV]

1

0.2

2

2

0.3

3

3

0.4

4

4

0.5

5

5

0.7

7

6

1.0

10

7

1.5

15

8

2

20

9

3

30

10

4

40

Отзывы: