Rockwell Automation Publication 1756-UM022D-EN-P - May 2017
109
Develop Safety Applications
Chapter 6
Produced/Consumed Safety
Tags
To transfer safety data between GuardLogix controllers, you use produced and
consumed safety tags. Produced and consumed tags require connections. The
default connection type for produced and consumed tags is unicast.
Produced and consumed safety tags are subject to the following restrictions:
• Only controller-scoped safety tags can be shared.
• Produced and consumed safety tags are limited to 128 bytes.
• Produced/consumed tag pairs must be of the same user-defined data
type.
• The first member of that user-defined data type must be the predefined
CONNECTION_STATUS data type.
• The requested packet interval (RPI) of the consumed safety tag must
match the safety task period of the producing GuardLogix controller.
To properly configure produced and consumed safety tags to share data
between peer safety controllers, you must properly configure the peer safety
controllers, produce a safety tag, and consume a safety tag, as described below.
Configure the Peer Safety Controllers’ Safety Network Numbers
The peer safety controller is subject to the same configuration requirements as
the local safety controller. The peer safety controller must also have a safety
network number (SNN). The SNN of the peer safety controller depends on its
placement in the system.
Table 34 - Produced and Consumed Connections
Tag
Connection Description
Produced
A GuardLogix controller can produce (send) safety tags to other 1756 or 1768 GuardLogix
controllers.
The producing controller uses a single connection for each consumer.
Consumed
GuardLogix controllers can consume (receive) safety tags from other 1756 or 1768
GuardLogix controllers.
Each consumed tag consumes one connection.
Table 35 - SNN and Controller Placement
Peer Safety Controller Location
SNN
Placed in the local chassis
GuardLogix controllers in a common chassis have the same SNN.
Placed in another chassis
The controller must have a unique SNN.
Содержание GuardLogix 5570
Страница 8: ...8 Rockwell Automation Publication 1756 UM022D EN P May 2017 Table of Contents...
Страница 20: ...20 Rockwell Automation Publication 1756 UM022D EN P May 2017 Chapter 1 System Overview Notes...
Страница 46: ...46 Rockwell Automation Publication 1756 UM022D EN P May 2017 Chapter 2 Install the Controller Notes...
Страница 56: ...56 Rockwell Automation Publication 1756 UM022D EN P May 2017 Chapter 3 Configure the Controller Notes...
Страница 124: ...124 Rockwell Automation Publication 1756 UM022D EN P May 2017 Chapter 6 Develop Safety Applications Notes...
Страница 134: ...134 Rockwell Automation Publication 1756 UM022D EN P May 2017 Chapter 7 Go Online with the Controller Notes...
Страница 162: ...162 Rockwell Automation Publication 1756 UM022D EN P May 2017 Appendix B Change ControllerType Notes...
Страница 169: ...Rockwell Automation Publication 1756 UM022D EN P May 2017 169 Index Notes...
Страница 170: ...170 Rockwell Automation Publication 1756 UM022D EN P May 2017 Index Notes...
Страница 171: ......