Publication 1794-6.5.16 – September 1998
Specifications – 1794-IP4 4 Channel Pulse Counter Module
Number of Inputs
4 pulse counter interfaces – 2 inputs each
Counting Frequency
100KHz maximum. Each signal condition must
be stable for at least 2
µ
s to be recognized.
Input Range
Input ON
Input OFF
Maximum 26.4V dc (24V dc +10%)
Minimum 6V dc
Maximum 3V dc
Minimum –26.4V dc
Input Current (typical)
3mA @ 6V dc
9mA @ 12V dc
15mA @ 24V dc
Module Location
Mounts on Cat. No. 1794-TB2, TB3, -TB3S,
and -TBN Terminal Base Units
Isolation Voltage
500V dc
Flexbus Current
5mA @ 5V dc
Power Supply (external)
12–24V dc (+10%)
Current consumption from
external power supply
150mA @ 12V dc
75mA @ 24V dc
Power Dissipation
5W maximum @ 26.4V dc
Thermal Dissipation
Maximum 17.1 BTU/hr @ 26.4V dc
Indicators (field side driven,
logic side indication)
1 green/red power/status indicator
8 yellow status indicators – logic side
8 yellow measurement function indicators
Keyswitch Position
1
Specifications continued on the next page.