48
FLEX Ex 8 Output and HART Analog Modules
Publication
1797-IN003J-EN-P - August 2017
Table 2
IMPORTANT
A terminal base may or may not have an I/O module
installed.
Terminals
V
t
(V)
I
t
(mA)
Groups
C
a
(
μ
F)
L
a
(
μ
H)
Male Bus
Connector
5.8
400
A to G
3.0
3.0
Hazardous (Classified) Location
Class I, Zones 0 Groups IIC, IIB, IIA
Class I, Div. 1 Groups A, B, C, D
Class II, Div. 1 Groups E, F, G
Class III, Div. 1
Hazardous (Classified) Location
Class I, Zones 1 Groups IIC
Class I, Div. 1 Groups A, B, C, D
For connection to other
modules, refer to the
General FM Certification
Information on page 29-1 of
publication 1797-RM001.
From FM approved devices,
1797-PS1N, -PS2N, or
-PS2N2.
For connection to other
modules, refer to the General
FM Certification Information on
page 29-1 of publication
1797-RM001.
1797-OE8 or
-OE8H
16
Shield Connection Only
50
51
35
34
V
max
=5.8V
I
max
=400mA
C
i
=1350nF
L
i
=negligible
V
max
=9.5V
I
max
=1A
C
i
=negligible
L
i
=negligible
Male Bus
Connector
33
40
41
42
43
44
45
0 (+)
Female Bus
Connector
1 (sig)
ch0
ch1
ch2
ch3
ch4
ch5
ch6
ch7
42056
Any Simple Apparatus
or FM
approved device with Entity
Concept parameters
(V
max
,
I
max
, C
i
, L
i
) appropriate for
connection to associated
apparatus with Entity Concept
parameters listed in Table 1.
2 (-)
4 (+)
5 (sig)
6 (-)
8 (+)
9 (sig)
10 (-)
12 (+)
13 (sig)
14 (-)
17 (+)
18 (sig)
19 (-)
21 (+)
22 (sig)
23 (-)
25 (+)
26 (sig)
27 (-)
29 (+)
30 (sig)
31 (-)