FLEX Ex 8 Output and HART Analog Modules
Publication
1797-IN003J-EN-P - August 2017
Field Descriptions
Analog/Digital
Output Mode
Selects if the channel acts as a normal analog output or as a switched
digital output.
Analog Output mode will follow the Analog Data Format selected.
Digital Output mode will output 0 mA = OFF, 22 mA = ON if the Fault
mode is 0 = disable. Digital Output mode will output 2 mA = OFF,
22 mA = ON if the Fault mode is 1 = wire off fault detection enabled.
Range: 0 = normal analog output, 1 = switched digital output.
Analog Output Data
Specifies the value of the analog output data to the module. Specific
format is controlled by Module Data Format Control parameter. This
data is used when the channel is in Analog Output mode.
Digital Output Data
Specifies the value of the digital output data to the module. This data
is used when the channel is in digital output mode.
Range: 0 = output, 0 mA = OFF, 1 = 22 mA = ON if the Fault mode is 0 =
disable. 0 = output, 2 mA = OFF, 1 = 22 mA = ON if the Fault mode is 1
= wire-off fault detection enabled.
Global Reset
This bit acts to reset all outputs to accept normal system output data.
It acts in conjunction with the Latch Retry parameter. If any channel
faults occur, the Latch Retry parameter can be set to cause the fault to
be latched and the output to go to its safe state value.
This is an edge-triggered signal. It must first be set (1). Reset will then
occur on the set-to-reset transition.
Output Enable
Signals module that communications has been interrupted to the
network. Output modules should execute their fault routine or go to
safe state.
On power-up, the module remains OFF, 0 mA out.
After normal power-up, this bit must be set (1) by the user program to
begin normal module functioning. If the bit is reset to 0 by a
communication fault, the module should use the information contained
in the Module Safe State data until the value is set to 1, when normal
function continues.
Analog Fault State
Determines how module reacts to faults when channel is used in
Analog Normal mode.
Range: 0 = go to minimum value of data range, 1 = go to maximum
value of data range, 2 = hold last state, 3 = 50% of data range
(1797-OE8) or use analog fault state value (1797-OE8H).