![Allen-Bradley ControlNet PCI 1784-PCIC Скачать руководство пользователя страница 15](http://html1.mh-extra.com/html/allen-bradley/controlnet-pci-1784-pcic/controlnet-pci-1784-pcic_installation-instructions-manual_2900555015.webp)
ControlNet PCI Communication Interface Card
15
Publication 1784-IN003A-EN-P - October 2000
Specifications
The operating parameters describe the environment within the card’s slot. Refer to
your computer documentation for environmental requirements. The card should
not exceed those specifications.
•
no other nodes
present on network
•
add other nodes to the network
flashing red/green
•
incorrect node
address
•
change PCIC/PCICS node address so that it is
less than or equal to UMAX
1
•
stop and restart the PCIC/PCICS driver in RSLinx
•
incorrect network
configuration
•
reconfigure the ControlNet network so that
UMAX
1
is greater than or equal to the PCIC/
PCICS node address
1
UMAX is the highest node address on a ControlNet network that can transmit data.
ATTENTION
!
This product must be mounted within a suitable system
enclosure to prevent personal injury resulting from
accessibility to live parts. The interior of this enclosure must
be accessible only by the use of a tool.
This industrial control equipment is intended to operate in a
Pollution Degree 2 environment, in overvoltage category II
applications, (as defined in IEC publication 664A) at altitudes
up to 2000 meters without derating.
Table D Specifications
General Specifications
Characteristic
Value
Power Requirements
5 V dc, 700 mA Maximum, Class 2
Conductor
Category 2
Use this conductor category information when you plan conductor
routing as described in publication 1770-4.1, Industrial Automation
Wiring and Grounding Guidelines.
Table C ControlNet status interpretation
A and
B
Cause:
Action:
AB Parts