        ControlNet PCI Communication Interface Card     

Publication 1784-IN003A-EN-P - October 2000 Year

Table C  ControlNet status interpretation

 A      and   

 B

Cause:

Action:

off

no power

none or apply power to the PC

PCIC/PCICS driver not 

started

start RSLinx

verify that the PCIC/PCICS driver has been 
configured properly in RSLinx

faulted card

check operating system event log for details of 
fault (if the PC’s operating system supports an 
event log)

cycle power to the PC

verify that you have firmly inserted the PCIC/
PCICS card into a PCI local bus expansion slot 
and that the expansion slot screw is tightened

if fault persists, contact your Rockwell 
Automation representative or distributor

see page 4 for technical support information

steady red

faulted card

check operating system event log for details of 
fault (if the PC’s operating system supports an 
event log)

cycle power to the PC

verify that you have firmly inserted the PCIC/
PCICS card into a PCI local bus expansion slot 
and that the expansion slot screw is tightened

if fault persists, contact your Rockwell 
Automation representative or distributor

see page 4 for technical support information

alternating red/green

self-test

none

alternating red/off

incorrect node 

configuration

duplicate ControlNet 

node address

check PCIC/PCICS node address and other 
ControlNet configuration parameters

off

channel disabled

program network for redundant
media, if required

steady green

normal operation

none

flashing green/off

temporary network 
errors

check media for broken cables, loose 

connectors, missing terminators, etc.

if condition persists, refer to the ControlNet 

Planning and Installation Manual, publication 
1786-6.2.1

flashing red/off

media fault

check media for broken cables, loose 

connectors, missing terminators, etc.

if condition persists, refer to the ControlNet 

Planning and Installation Manual, publication 
1786-6.2.1

Содержание ControlNet PCI 1784-PCIC

Страница 1: ...olNet monitoring and configuration capabilities The 1784 PCICS communication interface card provides ControlNet I O bridging as well as monitoring and configuration capabilities This document describe...

Страница 2: ...ndards The illustrations charts sample programs and layout examples shown in this guide are intended solely for purposes of example Since there are many variables and requirements associated with any...

Страница 3: ...information that is critical for successful application and understanding of the product About the Application Software The Allen Bradley standard application programming interface API is RSLinxTM sof...

Страница 4: ...ranty support support service agreements Obtain Pre Sales Product Support If you need to contact Rockwell Automation for pre sales product support try one of the following methods Call your local Rock...

Страница 5: ...ric Emission Standard Part 2 Industrial Environment EN 50082 2 EMC Generic Immunity Standard Part 2 Industrial Environment This product is intended for use in an industrial environment Low Voltage Dir...

Страница 6: ...nstall the card be certain that you know how to install hardware in your computer consult your computer s documentation for hardware installation instructions ATTENTION The card uses CMOS technology w...

Страница 7: ...ect a vacant PCI local bus expansion slot 4 Loosen the screw on the back rear bracket of the computer 5 Remove the slot s expansion cover 6 Insert the card To insert the card inside the computer 1 Fol...

Страница 8: ...page 12 See Figure 1 on page 8 for the connectors and indicators Figure 1 1784 PCIC or PCICS card 1784 PCIC card shown A B Network Access Port NAP RJ 45 connector for connecting programming terminals...

Страница 9: ...re than one ControlNet network to this card If you attempt to connect a second network to this card your communication system will operate erratically If you connect or disconnect the ControlNet cable...

Страница 10: ...ring for 1786 CP connector cable Connector 1 Wire Number Signal Mnemonic Signal Name 1 ISO GND Isolated Ground 2 N C No Connection 3 PTTX H Transmit Data High 4 PTTX L Transmit Data Low 5 PTRX L Recei...

Страница 11: ...does not support redundant media connect the tap dropline to the BNC connector labeled channel A Channel B is left open If the cable system is redundant connect the product so that all devices on the...

Страница 12: ...he instructions in these publications ControlNet Tap Installation Instructions publication 1786 5 7 ControlNet COAX Media Planning and Installation Manual publication CNET IN002A EN P Figure 5 Connect...

Страница 13: ...stems Windows NT 4 0 SP3 Windows 98 Windows 2000 Interpret the Status Indicators on the 1784 PCIC and PCICS The status indicators on the card give you information about the card and the network when y...

Страница 14: ...upports an event log cycle power to the PC verify that you have firmly inserted the PCIC PCICS card into a PCI local bus expansion slot and that the expansion slot screw is tightened if fault persists...

Страница 15: ...the highest node address on a ControlNet network that can transmit data ATTENTION This product must be mounted within a suitable system enclosure to prevent personal injury resulting from accessibilit...

Страница 16: ...5 to 95 without condensation Vibration 10 th 150 Hz constant 012 in displacement 10 to 150 Hz constant 2 0G acceleration not applicable Shock 30G peak 11 ms 50G peak 11 ms Agency Certification when p...

Страница 17: ...ivision 2 If this product contains batteries they must only be changed in an area known to be nonhazardous Informations sur l utilisation de cet quipement en environnements dangereux Les produits marq...

Страница 18: ...ion 1784 5 40 March 2000 2000 Rockwell International Corporation Printed in the U S A ControlNet is a trademark of ControlNet International Allen Bradley is a trademark of Rockwell Automation RSLinx i...

Отзывы: