Rockwell Automation Publication 1756-RM010C-EN-P - August 2018
Chapter 1
Update Considerations
Install the Redundancy
Firmware Bundle
This section details how to install the Redundancy Firmware Bundle.
• If you are updating from revision 20.05x to revision 24.052, see
Install the Revision 24.052 Redundancy Firmware Bundle on page 14
.
• If you are updating from revision 24.052 to revision 30.051, see
Install the Revision 30.051 Redundancy Firmware Bundle on page 16
.
• If you are updating from revision 30.051 to revision 31.052, see
Install the Revision 31.052 Redundancy Firmware Bundle on page 18
.
Install the Revision 24.052 Redundancy Firmware Bundle
If you are updating from revision 20.05x to revision 24.052, follow the steps in
this section.
Before you update software for your redundant system, use one of these
methods to shut down RSLinx Classic software:
• Right-click the RSLinx Classic icon in the notification area of the screen
and choose Shutdown RSLinx Classic.
• With RSLinx Classic software open, from the File menu, choose Exit
and Shutdown.
1. Browse to the location of the redundancy firmware revision 24.052_kit1
2. Unzip the redundancy firmware kit on your computer.
3. Browse to the directory on your computer that has the redundancy
firmware bundle, and unzip the Redundancy Module Configuration
Tool version 8.3.1.0 on your computer.
4. Browse to the directory on your computer that has the redundancy
firmware kit, and double-click ControlFlash.msi.
5. When the installation is complete, a dialog appears.