ControlLogix™ Sourcing Current Loop Input Module
19
Publication
1756-IN579A-EN-P - March 2003
ESD Immunity
IEC 61000-4-2:
6kV contact discharges
8kV air discharges
Radiated RF Immunity
IEC 61000-4-3:
10V/m with 1kHz sine-wave 80%AM from 30MHz to
2000MHz
10V/m with 200Hz 50% Pulse 100%AM at 900Mhz
EFT/B Immunity
IEC 61000-4-4:
±2kV at 5kHz on signal ports
Surge Transient Immunity
IEC 61000-4-5:
±2kV line-earth(CM) on shielded ports
Conducted RF Immunity
IEC 61000-4-6:
10Vrms with 1kHz sine-wave 80%AM from 150kHz to
80MHz
Enclosure Type Rating
None (open-style)
Certifications: (when product is
marked)
UL
UL Listed Industrial Control Equipment
CSA
CSA Certified Process Control Equipment
CSA
CSA Certified Process Control Equipment for
Class I, Division 2 Group A,B,C,D Hazardous
Locations
CE
(5)
European Union 89/336/EEC EMC Directive,
compliant with:
EN 50082-2; Industrial Immunity
EN 61326; Meas./Control/Lab., Industrial
Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
C-Tick
(5)
Australian Radiocommunications Act,
compliant with:
AS/NZS CISPR 11; Industrial Emissions
(1)
These specifications are notch filter dependant.
(2)
Maximum wire size will require extended housing - 1756-TBE.
(3)
Use this conductor category information for planning conductor routing as described in the system
level installation manual.
(4)
Refer to publication 1770-4.1
Industrial Automation Wiring and Grounding Guidelines
.
(5)
See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and
other certification details.