Allen-Bradley ControlLogix 1756-IF6CIS Скачать руководство пользователя страница 12

12

    ControlLogix™ Sourcing Current Loop Input Module 

Publication

 1756-IN579A-EN-P - March 2003

Figure 2 1756-IF6CIS – 4-wire transmitter connected to the module 
and an external, user-provided power supply providing 24V dc 
loop power

+

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

VOUT-1

IN-1/I

RTN-1

VOUT-3

IN-3/I

RTN-3

Not used

VOUT-5

IN-5/I

RTN-5

VOUT-0

IN-0/I

RTN-0

VOUT-2

IN-2/I

RTN-2

Not used

VOUT-4

IN-4/I

RTN-4

4-Wire 

Transmitter

43470

24V dc

Shield ground

+

NOTE: If separate power sources are used, do not exceed the specified 

isolation voltage.

Содержание ControlLogix 1756-IF6CIS

Страница 1: ...e visit www theautomationbookstore com and place an order call 800 963 9548 USA Canada or 001 320 725 1574 outside USA Canada To See page Obtain a User Manual 1 Identify the Module Components 4 Note t...

Страница 2: ...in this publication Allen Bradley publication SGI 1 1 Safety Guidelines for the Application Installation and Maintenance of Solid State Control available from your local Rockwell Automation office de...

Страница 3: ...enclosure must be accessible only by the use of a tool Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply...

Страница 4: ...el If you did not receive these components contact your local distributor Rockwell Automation sales office This module mounts in a 1756 chassis and uses a separately ordered RTB or a Bulletin 1492 Int...

Страница 5: ...e the Power Requirements This module receives power from the 1756 chasis power supply and requires 2 sources of power from the backplane 250mA at 5 1V dc 275mA at 24V dc Add this current power value 7...

Страница 6: ...xcessive wear to contacts on both the module and its mating connector Worn contacts may create electrical resistance that can affect module operation 1 Align the circuit board with the top and bottom...

Страница 7: ...module that correspond to unkeyed positions on the RTB For example if you key the first position on the module leave the first position on the RTB unkeyed 1 To key the module insert the U shaped band...

Страница 8: ...e RTB terminations can accommodate 22 14 AWG shielded wire Connect grounded end of the cable 1 Prepare one end of the cable for grounding WARNING When you connect or disconnect the Removable Terminal...

Страница 9: ...ab Use any chassis mounting tab that is designated as a functional earth ground terminal This symbol appears near the tab Chassis mounting tab Drain wire with ground lug 4M or 5M 10 or 12 phillips scr...

Страница 10: ...Clamp RTB A Strip 7 16 inch 11mm maximum length of wire B Insert the screwdriver into the inner hole of the RTB C Insert the wire into the open terminal and remove the screwdriver NEMA Screw RTB A Str...

Страница 11: ...below show how to wire the module Figure 1 1756 IF6CIS 2 wire transmitter connected to the module and the module providing 24V dc loop power 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 VOUT 1...

Страница 12: ...er provided power supply providing 24V dc loop power 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 VOUT 1 IN 1 I RTN 1 VOUT 3 IN 3 I RTN 3 Not used VOUT 5 IN 5 I RTN 5 VOUT 0 IN 0 I RTN 0 VOUT 2...

Страница 13: ...ter completing field side wiring secure the wires in the strain relief area with a cable tie 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 VOUT 1 IN 1 I RTN 1 VOUT 3 IN 3 I RTN 3 Not used VOUT 5...

Страница 14: ...e module is unlocked WARNING When you connect or disconnect the Removable Terminal Block RTB with field side power applied an electrical arc can occur This could cause an explosion in hazardous locati...

Страница 15: ...necessary LED indicators This display Means Take this action OK Steady green light The inputs are being multicast and in normal operating state None OK Flashing green light 1 The module has passed in...

Страница 16: ...ove the Module WARNING When you insert or remove the module while backplane power is on an electrical arc can occur This could cause an explosion in hazardous location installations Be sure that power...

Страница 17: ...aximum Sourcing Current Current limited to 30mA maximum Open Circuit Detection Time Zero reading within 5 seconds Overvoltage Protection 30V AC DC with PTC and Sense Resistor Normal Mode Noise Rejecti...

Страница 18: ...driver Blade Width for RTB 5 16 inch 8mm maximum Environmental Conditions Operating Temperature IEC 60068 2 1 Test Ad Operating Cold IEC 60068 2 2 Test Bd Operating Dry Heat IEC 60068 2 14 Test Nb Ope...

Страница 19: ...ment CSA CSA Certified Process Control Equipment for Class I Division 2 Group A B C D Hazardous Locations CE 5 European Union 89 336 EEC EMC Directive compliant with EN 50082 2 Industrial Immunity EN...

Страница 20: ...yst me le code de temp rature le plus d favorable code de temp rature le plus faible peut tre utilis pour d terminer le code de temp rature global du syst me Les combinaisons d quipements dans le syst...

Отзывы: