Dry I/O Contacts

T

here is one Remote Enable/Disable Switch connection and 3 Dry I/O Contacts available on the front of the 

UPS.  Do not apply external power to the Remote Enable/Disable Switch; however, the 3 sets of Dry Contacts 

required external power supplies (Contacts Rating is 1A/24 Vdc).  Each of the Dry Contacts is used to provide a 

remote status indication of the UPS as follows: 

 

1 and 2  On Battery Contact (NO)
3 and 4  Low Battery Contact (NO)
5 and 6 Fault 

(Indicates UPS has faulted see the User Manual trouble 

shooting section)

7 and 8  Remote Enable/Disable 

(Closed for Output Enable, Open for Output Disable)

 

USB Communication Port

T

he UPS supports a USB communication port for the end user to connect with a computer.  The 

user may monitor all the UPS status through the USB port if the 1609 UPS Management 

Software is installed in the computer.  The software is stored in the CD and can be found in the 

accessory bag.

Manual or Remote Enable / Disable of UPS Output Selection

T

he 1609-B UPS output is designed to be manually or remotely Enabled or Disabled.  User is required to 

enable or disable the remote function switch on the front panel.

Selected 'DISABLE' for Manual Enable/Disable the UPS's Output.

Selected 'ENABLE' for Remote Enable/Disable the UPS's Output.

Manual Enable/Disable/Self-test

T

he Power Button on the front of the UPS is used to manually enable or disable the output of the 1609-B UPS.

To enable the 1609-B UPS, press and hold the Power Button until one beep is 

heard.

T

o disable the 1609-B UPS, press and hold the Power Button until three beeps 

are heard then release immediately (takes approximately 3 seconds).

T

o perform a self-test, press and hold the Power Button until two beeps are 

heard then release immediately.

 

Bulletin 1609 Industrial Uninterruptible Power Supply

6

8 7 6 5 4 3 2 1

Publication 

1609-IN013B-EN-P -  August 2012

                     DIR 

10000234490 (Version 01)

 

REMOTE FUNCTION

ENABLE

DISABLE

 

 

Содержание Bulletin 1609

Страница 1: ...the battery compartment Battery Harness inside the battery compartment Additional Resources 1 Go to http www rockwellautomation com literature 2 Go to Search select Publication Number 3 Type the Publ...

Страница 2: ...a at surface Use the provided jumper wire to connect the batteries in series Connect the positive terminal red of the battery to the negative terminal black of another battery Connect the red wire of...

Страница 3: ...e Diagram 2 below Diagram 1 Standard DIN Rail Mount Diagram 2 Optional Panel or Floor Mount Batteries Wiring and Installation Instruction for the UPS Cont d 5 To complete the battery installation clos...

Страница 4: ...Minimum temperature 75 C Wire conductor material Copper only Tightening torque for terminals 4 4 lb in Warning To reduce the risk of fire connect only to a circuit provided with 20 amperes maximum bra...

Страница 5: ...a Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required precautions Keep unauthorized personnel away from the batteries b When replacing ba...

Страница 6: ...software is stored in the CD and can be found in the accessory bag Manual or Remote Enable Disable of UPS Output Selection The 1609 B UPS output is designed to be manually or remotely Enabled or Disab...

Страница 7: ...Version 01 L E N L E AC Input AC Output Backfeed Relay Inverter Relay AC to DC Charger DC to DC DC to AC Step Wave Backfeed Relay Input Filter N Indicator LED Indicator Title On Line The UPS is supply...

Страница 8: ...Styrofoam beads for packaging Damage sustained in transit is not covered under warranty DIR 10000234490 Version 01 Copyright 2012 Rockwell Automation Inc All Rights Reserved Printed in China Allen Br...

Отзывы: