Allen-Bradley Bulletin 1609 Скачать руководство пользователя страница 4

Bulletin 1609 Industrial Uninterruptible Power Supply

4

Publication 

1609-IN013B-EN-P -  August 2012

                     DIR 

10000234490 (Version 01)

 

Hardwire UPS

Wiring of the UPS should be performed by a qualified electrician using the appropriate wire gauges.

Selection of Cables:

AC Main Input / Output Wiring for UPS:

Connect Power and Equipment to the UPS

1. 

Connect the appropriate input power to the UPS's input (Line, Neutral and Ground) terminals (see 

Diagram 3).

2.  

Connect the specified equipment to the UPS's output (Line, Neutral and Ground) terminals (see 

Diagram 3).

Diagram 3 - System Wiring

Item

Specification

Wire si

z

e

14 AWG

Minimum temperature

75°C

Wire conductor material

Copper only

T

ightening torque for terminals

4

.

4 lb-in

Warning:  

To reduce the risk of fire, connect only to a circuit provided with 20 amperes maximum branch circuit overcurrent 

protection in accordance with the National Electric Code, ANSI/NFPA 70.
A disconnect switch shall be provided by others for AC output circuit.  To reduce the risk of fire, connect only to a circuit 
provided with branch circuit overcurrent protection for 20 amperes rating in accordance with the National Electric Code, 
ANSI/NFPA 70.

Warning: 

This UPS features Surge Protective Device (SPD) located on the top of the unit.  Please disconnect all power 

sources before servicing due to Electric Shock Hazard for risk of severe injury or death.'

INPUT

L

L

N

N

G

G

OUTPUT

AC Output

AC Input

Содержание Bulletin 1609

Страница 1: ...the battery compartment Battery Harness inside the battery compartment Additional Resources 1 Go to http www rockwellautomation com literature 2 Go to Search select Publication Number 3 Type the Publ...

Страница 2: ...a at surface Use the provided jumper wire to connect the batteries in series Connect the positive terminal red of the battery to the negative terminal black of another battery Connect the red wire of...

Страница 3: ...e Diagram 2 below Diagram 1 Standard DIN Rail Mount Diagram 2 Optional Panel or Floor Mount Batteries Wiring and Installation Instruction for the UPS Cont d 5 To complete the battery installation clos...

Страница 4: ...Minimum temperature 75 C Wire conductor material Copper only Tightening torque for terminals 4 4 lb in Warning To reduce the risk of fire connect only to a circuit provided with 20 amperes maximum bra...

Страница 5: ...a Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the required precautions Keep unauthorized personnel away from the batteries b When replacing ba...

Страница 6: ...software is stored in the CD and can be found in the accessory bag Manual or Remote Enable Disable of UPS Output Selection The 1609 B UPS output is designed to be manually or remotely Enabled or Disab...

Страница 7: ...Version 01 L E N L E AC Input AC Output Backfeed Relay Inverter Relay AC to DC Charger DC to DC DC to AC Step Wave Backfeed Relay Input Filter N Indicator LED Indicator Title On Line The UPS is supply...

Страница 8: ...Styrofoam beads for packaging Damage sustained in transit is not covered under warranty DIR 10000234490 Version 01 Copyright 2012 Rockwell Automation Inc All Rights Reserved Printed in China Allen Br...