Get Started
Multi-mode Express Setup
Multi-mode Express Setup has three modes:
•
Short Press mode—You want to use Express Setup to enter the initial IP
address of the switch. You can then configure additional network
settings via Device Manager. To run Short Press mode, see
.
•
Medium Press mode—You want to use a DHCP server to assign the
switch an IP address. You can then configure additional network
settings via Device Manager or the Logix Designer application. To run
Medium Press mode, see
.
•
Long Press mode—You want to reset the switch to use factory default
settings. To run Long Press mode, see
summarizes the function of each mode.
IMPORTANT
The Studio 5000 Logix Designer® application supports only Medium-press
mode.
Table 9 - Mulit-mode Express Setup Modes
Attribute
Short Press Mode
Medium Press Mode
Long Press Mode
Enable method
Press and hold the Express Setup button until the
Setup status indicator flashes green during
seconds 1…5, and then release.
Press and hold the Express Setup button until the
Setup status indicator flashes red during seconds
6…10, and then release.
Press and hold the Express Setup button until the
Setup status indicator flashes alternating green
and red during seconds 16…20, and then
release.
Between seconds 11…15 and after 21 seconds, the Setup status indicator turns off. If you release the
Express Setup button while the Setup status indicator is off, no Express Setup mode is enabled.
Setup status indicator
Flashes green between seconds 1…5.
Flashes red between seconds 6…10.
Flashes green and red between seconds 16…20.
Function
•
The Express Setup management interface is
selected.
•
The switch acts as a DHCP server on
VLAN 1000 with an address of 169.254.0.1.
•
Once the DHCP session is successfully
established, the switch assigns the computer
an IP address of 169.254.0.2 on VLAN 1000.
•
The default login credentials are set to the
following:
–
User name: [no user name/blank]
–
Password:
switch
•
Express Setup parameters are completed via
Device Manager.
•
A DHCP client request is sent out of all switch
ports on VLAN 1.
•
VLAN 1 is configured with the IP address
returned by DHCP.
•
The default login credentials are set to the
following:
–
User name: [no user name/blank]
–
Password:
switch
•
CIP (Common Industrial Protocol) is enabled
on VLAN 1 with the CIP Security password set
to
switch
.
•
Express Setup parameters are completed via
Device Manager or the Logix Designer
application.
•
All configuration settings (config.text,
vlan.dat, and private-config.text files) in
internal memory or on the SD card or
CompactFlash card are reset to factory
defaults.
•
The switch restarts with factory default
settings.
Содержание armorstratix 5700
Страница 10: ...10 Rockwell Automation Publication 1783 UM007I EN P December 2017 Table of Contents Notes ...
Страница 12: ...12 Rockwell Automation Publication 1783 UM007I EN P December 2017 Preface Notes ...
Страница 72: ...72 Rockwell Automation Publication 1783 UM007I EN P December 2017 Chapter 2 Get Started Notes ...
Страница 148: ...148 Rockwell Automation Publication 1783 UM007I EN P December 2017 Chapter 3 Configure Switch Features ...
Страница 282: ...282 Rockwell Automation Publication 1783 UM007I EN P December 2017 Chapter 3 Configure Switch Features Notes ...
Страница 317: ...Rockwell Automation Publication 1783 UM007I EN P December 2017 317 Monitor the Switch Chapter 4 ...
Страница 319: ...Rockwell Automation Publication 1783 UM007I EN P December 2017 319 Monitor the Switch Chapter 4 ...
Страница 325: ...Rockwell Automation Publication 1783 UM007I EN P December 2017 325 Monitor the Switch Chapter 4 ...
Страница 338: ...338 Rockwell Automation Publication 1783 UM007I EN P December 2017 Chapter 5 Troubleshoot the Switch Notes ...
Страница 396: ...396 Rockwell Automation Publication 1783 UM007I EN P December 2017 Appendix A DataTypes Notes ...
Страница 404: ...404 Rockwell Automation Publication 1783 UM007I EN P December 2017 Appendix B Port Assignments for CIP Data Notes ...
Страница 450: ...450 Rockwell Automation Publication 1783 UM007I EN P December 2017 Appendix D Cables and Connectors Notes ...
Страница 457: ......