9
ArmorBlock-LP 16 Input Module
Publication 1792-5.6 – September 1997
Specifications
16 Input Module – Cat. No. 1792-IB16LP
Input Specifications
Inputs per Block
16 sinking
On-state Voltage Range
12–30V dc
On-state Current
Maximum
Minimum
15.0mA @ 30V dc
1.6mA @ 12V dc
Off-state Voltage
Maximum
5V dc
Off-state Current
Minimum
0.8mA
Transition Voltage
5–12.0V dc
Transition Current
0.8–2.2mA
Input Signal Delay
Off to On or On to Off
1ms maximum
Sensor Source
Voltage
Current
Minimum 13V dc @ 800mA out and
DeviceNet power = 15V dc
50mA per point, 0.8A total per module
Indicators
Network Status – red/green
Module Status – red/green
Sensor Power Supply Status – green
Module Power Supply Status – green
Short Circuit Sensors – red
I/O Status – yellow
Communication Rate in Baud
125k, 250k, 500k selectable
General Specifications
DeviceNet Power
Voltage
Current
11.0 – 25.0V dc
100mA (no powered sensors)
900mA (full sensor load)
Dimensions
Inches
Millimeters
6.0H X 2.4W X 2.0D
152H X 60W X 51D
Environmental Conditions
Operational Temperature
Storage Temperature
Relative Humidity
Shock
Operating
Non-operating
Vibration
0 to 60
o
C (32 to 140
o
F)
–20 to 80
o
C (–40 to 176
o
F)
up to 100%
30 g peak acceleration, 11(+1)ms pulse width
50 g peak acceleration, 11(+1)ms pulse width
Tested 10 g @ 10–500Hz per IEC 68-2-6
Specifications continued on next page.