ArmorBlock is a trademark of Allen-Bradley Co. Inc.

Publication 1792-5.6 – September 1997

    

Cat. No. 1792-IB16LP

This 1792 ArmorBlock

 I/O block module (Cat. No. 1792-IB16LP

)

contains I/O circuits, a built-in power supply, and a built-in DeviceNet
I/O adapter.  Because of its sealed housing, this 1792 I/O block requires
no enclosure.  It is compatible with PLC or SLC programmable
controllers using DeviceNet scanners.  The I/O values are accessible
from the PLC or SLC programmable controller data table.

This ArmorBlock-LP module has no switches to set. You set module
parameters using the DeviceNet Manager Software (cat. no. 1787-MGR)
or similar configuration tool.

Contents

This box contains:

1 ArmorBlock–LP module

Package containing 10 write-on indicator tabs, and 7 micro caps

1 DeviceNet right hand aluminum T-port tap (part number 97042401)

Installation Instructions

European Union Directive Compliance

If this product is installed within the European Union or EEA regions
and has the CE mark, the following regulations apply.

EMC Directive

This apparatus is tested to meet Council Directive 89/336/EEC
Electromagnetic Compatibility (EMC).

The product described in this manual is intended for use in an industrial
environment.

Installation Instructions

Содержание ArmorBlock-LP 1792-IB16LP

Страница 1: ...as no switches to set You set module parameters using the DeviceNet Manager Software cat no 1787 MGR or similar configuration tool Contents This box contains 1 ArmorBlock LP module Package containing 10 write on indicator tabs and 7 micro caps 1 DeviceNet right hand aluminum T port tap part number 97042401 Installation Instructions European Union Directive Compliance If this product is installed w...

Страница 2: ...770 4 1 Automation Systems Catalog publication B111 Install Your ArmorBlock Module Installation of the ArmorBlock module consists of setting the node address and communication rate in the ArmorBlock module mounting the ArmorBlock module connecting the wiring communicating with your module Set the Node Address Each ArmorBlock comes with its internal program set for node address 63 and a communicati...

Страница 3: ...rom 9V dc power supply adapter 1770 KFD RS 232 module Power Supply Open style connector to sealed mini connector Mount the ArmorBlock Module Mount the block module directly to the machine or device Complete mounting dimensions are shown below Mounting Dimensions 2 0 51 1 1 27 1 1 27 1 1 27 1 25 32 1 0 25 5 1 3 33 1 5 39 2 4 60 1 4 36 6 0 152 4 2 107 0 18 4 5 1 8 45 1 5 38 30198 M Use 3 8 4mm screw...

Страница 4: ... plugs to cover and seal unused ports Pinout diagrams for these connectors are shown below ATTENTION Make sure all connectors are securely tightened to properly seal the connections against leaks and maintain IP67 requirements Connecting the Input Wiring Connect input wiring to the micro connectors which screw into mating connectors on the front of the block Make connections as shown below 1 2 3 4...

Страница 5: ...nnection Consumes Produces Polled 0 Bytes 3 Bytes Bit Strobe 0 Bytes 3 Bytes Change of State 0 Bytes 3 Bytes Polled device a master initiates communication by sending its polled I O message to the ArmorBlock module The 16 input module scans the inputs and fault bit producing a response that reflects their status Change of state productions occur when an input changes or an input source voltage fau...

Страница 6: ...ces 3 IS Reserved Where I Input IS Sensor source voltage fault Word Bit Description Produces 1 00 07 Input bits bit 00 corresponds to input 1A bit 01 to input 2A and so on 0 input off 1 the input is on Produces 2 00 07 Input bits bit 00 corresponds to input 1B bit 01 to input 2B and so on 0 input off 1 the input is on Produces 3 00 06 Reserved 3 07 Sensor source voltage fault bit this bit is set 1...

Страница 7: ... Network Status Indicator OVL Sensor Short Circuit Indicator US Sensor Power Supply Status Indicator UL Module Power Supply Status Indicator A and B Input I O Status Indicators MS Module Status Indicator A B A B A B A B A B A B A B A B 1 2 3 4 5 6 7 8 Note This module contains a circuit to protect the DeviceNet power supply from short circuits in an attached sensor or sensor cable If you connect a...

Страница 8: ...twork access Flashing Green OFF On line but not connected Solid Green On line link okay connected Flashing Red Recoverable fault Solid Red Critical failure Sensor Short Circuit Indicator OVL Indication Status OFF Sensor source voltage operating correctly Solid Red 1 or more Sensor source voltage shorts Input I O Status Indicators A and B Indication Status OFF No valid input signal present Yellow V...

Страница 9: ...dule Indicators Network Status red green Module Status red green Sensor Power Supply Status green Module Power Supply Status green Short Circuit Sensors red I O Status yellow Communication Rate in Baud 125k 250k 500k selectable General Specifications DeviceNet Power Voltage Current 11 0 25 0V dc 100mA no powered sensors 900mA full sensor load Dimensions Inches Millimeters 6 0H X 2 4W X 2 0D 152H X...

Страница 10: ...Bulgaria Canada Chile China PRC Colombia Costa Rica Croatia Cyprus Czech Republic Denmark Ecuador Egypt El Salvador Finland France Germany Greece Guatemala Honduras Hong Kong Hungary Iceland India Indonesia Ireland Israel Italy Jamaica Japan Jordan Korea Kuwait Lebanon Malaysia Mexico Netherlands New Zealand Norway Pakistan Peru Philippines Poland Portugal Puerto Rico Qatar Romania Russia CIS Saud...