Configure the 857-RAD Analog Outputs
Appendix A
Example #3 – mA Output Scaling for Bidirectional Power
• Minimum Analog Output value = 4 mA
• Maximum Analog Output value = 20 mA
• Linked minimum value = -2000 kVAR
• Linked maximum value = 6000 kVAR
• Modbus minimum value = 4000
(Minimum Analog Output value x 1000)
• Modbus maximum value= 20,000
(Maximum Analog Output value x 1000)
Figure 15 - mA Output Scaling for Bidirectional Power