Installation Instructions

Original Instructions

Four-Circuit Direct Opening Action Limit Switch 

Catalog Numbers 802T 

Overview

Bulletin 802T Direct Opening Action limit switches have been 

designed for use in applications requiring control reliability 

performance per ANSI B11.19 and in safety applications
Limit switches are used in electrical control systems  to sense position. 

They are actuated by the predetermined motion of a cam, machine 

component or piece part. These limit switches are suitable for use in 

control systems requiring control reliability performance or safety 

related performance per ISO 13849–1.

Typical Example of a Dual Channel Safety Application

Before installation in a safety application, a risk assessment should be 

performed to determine whether the specifications of this device are 

suitable for foreseeable operational and environmental characteristics 

of the machine which is to be controlled. Only the normally closed set 

of contacts are considered safety contacts. When applying these limit 

switches in a safety system application, all applicable standards for 

application should be followed. Operating specifications must be 

followed and actuator must be displaced beyond the point where 

Direct Opening Action occurs. These devices are not to be used to 

directly control a motor.

General Data

• Safety Contacts: 2 Normally Closed
• Auxiliary Contacts: 2 Normally Open
• Enclosure Rating:

• NEMA 4, 6P, 12, and 13
• IP67

• Operating rate and speed 

1

 

• Lever Type: 150/minute @ 9 m (30 ft)/minute 

2

• Top Push Roller: 150/minute @ 9 m (30 ft)/minute 

3

• Side Push Roller: 150/minute @ 9 m (30 ft)/minute 

3

• Operating temperature (standard models) 18…110°C 

(0…230°F) 

• Short Circuit Protection: 10 amp slow or 15 amp fast

 

acting. 

Overload protection should be sized to load requirements.

Mounting

Limit switches should be securely mounted using the mounting holes 

provided. During installation, ensure that the actuator will be displaced 

beyond the point where Direct Opening Action takes place. Adjustable 

levers or rod actuators should not be used in safety systems 

applications.

1

Based on operation temperatures of 20…30°C (68…86°F).

2

Using 802T-W1A operating lever.

3

Using 30° non-overtravel dog.

Wiring

The pressure type connector terminals in the base will accept No. 

12 A

WG and smaller solid or stranded wire. For proper tightening, it is 

suggested that nothing smaller than No. 18 AWG be used. Before 

inserting wire under the pressure plates, strip the insulation 

approximately 3/8 inch. Tighten all pressure plate terminals whether 

used or not, to avoid interference with the switch cover.

ATTENTION: 

To avoid electrical shock and 

unintended operation of equipment, disconnect 
all power to the limit switch and the controlled 
equipment before proceeding with any repair or 
adjustment of the limit switch.

ATTENTION: 

Adjustable length lever actuators should not be used 

in a safety systems application.

1
2

5
6

3
4

7
8

Description

Tightening Torque

Terminal Screws

2.03 N•m (18 lb•in)

Front to Rear Base

1.81…2.26 N•m (16…20 lb•in)

Head Screws

1.35…2.03 N•m (12…18 lb•in)

Lever Arm

2.82…4.07 N•m (25…36 lb•in)

IMPORTANT

The contacts in each switching element must have the same 
polarity. The circuit diagram is shown on the nameplate.