Rockwell Automation Publication 5094-IN001B-EN-P - May 2018
5
FLEX 5000 EtherNet/IP Adapters with RJ45 Ports
About the Adapter
FLEX 5000 EtherNet/IP Adapter with RJ45 Ports
Before You Begin
Before you install the adapter, verify that you have the following:
Components Needed to Install a FLEX 5000 EtherNet/IP Adapter with RJ45 Ports
Component
Description
Removable terminal
block (RTB)
Your adapter comes with a screw-type RTB. You can order screw-type or spring-type RTBs separately:
• 5094-AENRTB-QTY5 – Ethernet Adapter RTB, Screw-type, Pack of 5
• 5094-AENRTBS-QTY5 – Ethernet Adapter RTB, Spring-type, Pack of 5
External power supply for
module power
A power supply that is adequately sized to provide module power, that is, system-side power, to the FLEX 5000 I/O modules.
For more information, see
Power Considerations on page 7
.
Tools
You need the following tools:
• Screwdriver
• Wire stripper
• Wires
For more information on available wire sizes and wire insulation stripping length, see
Specifications on page 14
.
DIN rail
Compatible zinc-plated, yellow-chromate steel DIN rail.
You can use a steel DIN rail such as the Allen-Bradley 199-DR1; 46277-3; EN50022 – 35 x 7.5 mm (1.38 x 0.30 in.).
EtherNet/IP network
components
You must install the network and all required components.
Software
If you do not use the rotary switches to set the adapter IP address, you can use the following software to set the IP address:
• DHCP server
• BootP DHCP EtherNet/IP Commissioning Tool
• RSLinx® Classic software
For more information, see
Set the Network Internet Protocol (IP) Address on page 7
.
STATUS
NET
LINK 1
LINK 2
5094-AENTR
EtherNet/IP
™
Adapter
FLEX 5000
TM
I/O
PRP
DLR
POWER
X100
X10
X1
IP ADDRESS
Reset lever
Status indicators
IP address label
IP address rotary switches
Power RTB
Ethernet port 1
Ethernet port 2
Functional earth
(1)
PRP/DLR switch
(2)
DIN rail latch
(1) Functional earth must be grounded. See
Ground Considerations on page 7
for more information.
(2) Refer to the following IMPORTANT statement about the PRP/DLR switch for more information.
IMPORTANT
You must set the PRP/DLR switch to the DLR position. If you set the switch to the PRP position, the adapter cannot establish connection with the
I/O modules.
Ethernet address