Rockwell Automation Publication 5094-IN001B-EN-P - May 2018

5

FLEX 5000 EtherNet/IP Adapters with RJ45 Ports

About the Adapter

FLEX 5000 EtherNet/IP Adapter with RJ45 Ports

Before You Begin

Before you install the adapter, verify that you have the following:

Components Needed to Install a FLEX 5000 EtherNet/IP Adapter with RJ45 Ports

Component

Description

Removable terminal 
block (RTB)

Your adapter comes with a screw-type RTB. You can order screw-type or spring-type RTBs separately:
• 5094-AENRTB-QTY5 – Ethernet Adapter RTB, Screw-type, Pack of 5
• 5094-AENRTBS-QTY5 – Ethernet Adapter RTB, Spring-type, Pack of 5

External power supply for 
module power

A power supply that is adequately sized to provide module power, that is, system-side power, to the FLEX 5000 I/O modules. 
For more information, see 

Power Considerations on page 7

Tools

You need the following tools:
• Screwdriver
• Wire  stripper
• Wires
For more information on available wire sizes and wire insulation stripping length, see 

Specifications on page 14

DIN rail

Compatible zinc-plated, yellow-chromate steel DIN rail. 
You can use a steel DIN rail such as the Allen-Bradley 199-DR1; 46277-3; EN50022 – 35 x 7.5 mm (1.38 x 0.30 in.).

EtherNet/IP network 
components

You must install the network and all required components.

Software

If you do not use the rotary switches to set the adapter IP address, you can use the following software to set the IP address:
• DHCP  server
• BootP DHCP EtherNet/IP Commissioning Tool
• RSLinx®  Classic  software
For more information, see 

Set the Network Internet Protocol (IP) Address on page 7

STATUS

NET

LINK 1

LINK 2

5094-AENTR

EtherNet/IP

 Adapter

FLEX 5000

TM

 I/O

PRP

DLR

POWER

X100

X10

X1

IP ADDRESS

Reset lever

Status indicators

IP address label

IP address rotary switches

Power RTB

Ethernet port 1

Ethernet port 2

Functional earth 

 

(1)

PRP/DLR switch 

(2)

DIN rail latch

(1) Functional earth must be grounded. See 

Ground Considerations on page 7

 for more information.

(2) Refer to the following IMPORTANT statement about the PRP/DLR switch for more information.

IMPORTANT

You must set the PRP/DLR switch to the DLR position. If you set the switch to the PRP position, the adapter cannot establish connection with the 
I/O modules.

Ethernet address

Содержание 5094-AEN2TR

Страница 1: ...94 AEN2TRXT adapters support as many as 16 FLEX 5000 I O modules The adapters are configured with the Studio 5000 Logix Designer application For more information on how to use FLEX 5000 EtherNet IP Ad...

Страница 2: ...encati nella sezione Altre risorse riguardanti l installazione la configurazione ed il funzionamento dell apparecchiatura Gli utenti devono leggere e comprendere le istruzioni di installazione e cabla...

Страница 3: ...dangereux Lorsque plusieurs produits sont combin s dans un syst me le code de temp rature le plus d favorable code de temp rature le plus faible peut tre utilis pour d terminer le code de temp rature...

Страница 4: ...touch connectors or pins on component boards Do not touch circuit components inside the equipment Use a static safe workstation if available Store the equipment in appropriate static safe packaging wh...

Страница 5: ...N rail Compatible zinc plated yellow chromate steel DIN rail You canuse a steel DIN rail such as the Allen Bradley 199 DR1 46277 3 EN50022 35 x 7 5 mm 1 38 x 0 30 in EtherNet IP network components You...

Страница 6: ...d adjacent equipment You can mount the DIN rail horizontally or vertically FLEX 5000 EtherNet IP Adapter with RJ45 Ports Spacing AdapterDimensions FLEX 5000 EtherNet IP Adapter with RJ45 Ports Dimensi...

Страница 7: ...onal Resources on page 15 SettheNetworkInternetProtocol IP Address FLEX 5000 EtherNet IP Adapters with RJ45 Ports ship DHCP enabled and with their rotary switches set to 999 If the network uses 192 16...

Страница 8: ...ublication ENET UM004 InstalltheAdapterontotheDINRail The adapter must be installed left most to the I O modules 1 Make sure that the DIN rail latch is in the Locked position 2 If the DIN rail latch i...

Страница 9: ...source is properly sized For example if the total module power current draw including current inrush requirements is 4 A you can use a power supply that is limited to 4 A 1 Verify that the external po...

Страница 10: ...1 mm2 14 AWG Strip 15 1 mm 0 59 0 04 in of insulation from the wires RTB Type Action Screw 1 Insert the wire into the terminal 2 Turn the screwdriver to close the terminal on the wire Torque the screw...

Страница 11: ...etwork anelectricarccanoccur This could cause an explosion in hazardous location installations Be sure that power is removed or the area is nonhazardous before proceeding This warning applies to conne...

Страница 12: ...damage or injury from electric shock can result 1 Make sure that the end cap is unlocked If the end cap is locked pull the tab until it clicks 2 Align the end cap with interlocking pieces on the last...

Страница 13: ...locked 6 Pull the adapter off the DIN rail 7 To replace the adapter repeat the installation steps that are described beginning at Set the Network Internet Protocol IP Address on page 7 ATTENTION Do no...

Страница 14: ...e 100 AM at 1890 MHz 10V m with 1 kHz sine wave 80 AM from 2000 2700 MHz EFT B Immunity IEC 61000 4 4 4 kV at 5 kHz on power ports 4 kV at 5 kHz on Ethernet ports Surge Transient Immunity IEC 61000 4...

Страница 15: ...0 Control Systems User Manual publication ENET UM004 Describes how to install configure and operate EtherNet IP Communication Modules in Logix 5000 Control Systems FLEX 5000 Digital I O Modules User M...

Страница 16: ...us serve your documentation needs better If you have any suggestions on how to improve this document complete the How Are We Doing form at http literature rockwellautomation com idc groups literature...

Отзывы: