14

Rockwell Automation Publication 5094-IN001B-EN-P - May 2018

FLEX 5000 EtherNet/IP Adapters with RJ45 Ports

Specifications

This table includes a subset of specifications for the adapter. For a complete list of specifications, see the FLEX 5000 Modules Specifications 
Technical Data, publication 

5094-TD001

Attribute

5094-AENTR

5094-AENTRXT

5094-AEN2TR

5094-AEN2TRXT

Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold)
IEC 60068-2-2 (Test Bd, Operating Dry Heat)
IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

-40 °C < Ta < +70 °C
(-40 °F < Ta < +158 °F)

Temperature, surrounding air, max

70 °C (158 °F)

Temperature, nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold)
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat)
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal 
Shock)

-40…+85 °C (-40…+185 °F)

Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration
IEC 60068-2-6 (Test Fc, Operating)

5 g @ 10…500 Hz

Shock, operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Shock, nonoperating
IEC 60068-2-27 (Test Ea, Unpackaged Shock)

30 g

Emissions

IEC 61000-6-4

ESD Immunity
IEC 61000-4-2

6 kV contact discharges
8 kV air discharges

Radiated RF Immunity
IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz
10V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B Immunity
IEC 61000-4-4

±4 kV at 5 kHz on power ports
±4 kV at 5 kHz on Ethernet ports

Surge Transient Immunity
IEC 61000-4-5

±1 kV line-line (DM) and ±2 kV line-earth (CM) on power ports
±2 kV line-earth (CM) on Ethernet ports

Conducted RF Immunity
IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Enclosure type rating

None (open-style)

Corrosion resistance classification

ISA S71.04 G3

ISA S71.04 G3

Voltage and current ratings, MP

18…32V DC, 1250mA

18…32V DC, 1880mA

Voltage and current ratings, MP inrush

18…32V DC, 3200mA for 100ms

18…32V DC, 5700mA for 100ms

Voltage and current ratings, backplane

15V DC, 1130mA

15V DC, 1800mA

Power dissipation, max

5.1 W @ 18V DC

6.2 W @ 18V DC

Thermal dissipation

17.4 BTU/hr @ 24V DC

21.1 BTU/hr @ 24V DC

Isolation voltage

300V (continuous), Basic Insulation Type
Tested at 2121V DC for 60 s, Power to Backplane and Backplane to Ethernet 
Tested at 4242V DC for 60 s, Power to Ethernet Ports
No isolation between Ethernet Ports

Wire size, Power RTB

0.33... 2.1 mm

2

 (22...14 AWG) solid or stranded copper wire rated at 105°C (221°F), or greater, 1.2 mm (3/64 in.) insulation max, single 

wire connection only. Ferrule according to DIN 46 228/1.

Wire size, functional earth terminal

2.1 mm

2

 (14 AWG) solid or stranded copper wire rated at 105 °C (221 °F), or greater, 3.5mm (0.14in) max diameter including 

insulation, single wire connection only. 

Terminal block torque, Power RTB

Screw-type RTB:
• 0.4 N•m (3.5 lb•in)
Spring-type RTB:
• Not applicable

Содержание 5094-AEN2TR

Страница 1: ...94 AEN2TRXT adapters support as many as 16 FLEX 5000 I O modules The adapters are configured with the Studio 5000 Logix Designer application For more information on how to use FLEX 5000 EtherNet IP Ad...

Страница 2: ...encati nella sezione Altre risorse riguardanti l installazione la configurazione ed il funzionamento dell apparecchiatura Gli utenti devono leggere e comprendere le istruzioni di installazione e cabla...

Страница 3: ...dangereux Lorsque plusieurs produits sont combin s dans un syst me le code de temp rature le plus d favorable code de temp rature le plus faible peut tre utilis pour d terminer le code de temp rature...

Страница 4: ...touch connectors or pins on component boards Do not touch circuit components inside the equipment Use a static safe workstation if available Store the equipment in appropriate static safe packaging wh...

Страница 5: ...N rail Compatible zinc plated yellow chromate steel DIN rail You canuse a steel DIN rail such as the Allen Bradley 199 DR1 46277 3 EN50022 35 x 7 5 mm 1 38 x 0 30 in EtherNet IP network components You...

Страница 6: ...d adjacent equipment You can mount the DIN rail horizontally or vertically FLEX 5000 EtherNet IP Adapter with RJ45 Ports Spacing AdapterDimensions FLEX 5000 EtherNet IP Adapter with RJ45 Ports Dimensi...

Страница 7: ...onal Resources on page 15 SettheNetworkInternetProtocol IP Address FLEX 5000 EtherNet IP Adapters with RJ45 Ports ship DHCP enabled and with their rotary switches set to 999 If the network uses 192 16...

Страница 8: ...ublication ENET UM004 InstalltheAdapterontotheDINRail The adapter must be installed left most to the I O modules 1 Make sure that the DIN rail latch is in the Locked position 2 If the DIN rail latch i...

Страница 9: ...source is properly sized For example if the total module power current draw including current inrush requirements is 4 A you can use a power supply that is limited to 4 A 1 Verify that the external po...

Страница 10: ...1 mm2 14 AWG Strip 15 1 mm 0 59 0 04 in of insulation from the wires RTB Type Action Screw 1 Insert the wire into the terminal 2 Turn the screwdriver to close the terminal on the wire Torque the screw...

Страница 11: ...etwork anelectricarccanoccur This could cause an explosion in hazardous location installations Be sure that power is removed or the area is nonhazardous before proceeding This warning applies to conne...

Страница 12: ...damage or injury from electric shock can result 1 Make sure that the end cap is unlocked If the end cap is locked pull the tab until it clicks 2 Align the end cap with interlocking pieces on the last...

Страница 13: ...locked 6 Pull the adapter off the DIN rail 7 To replace the adapter repeat the installation steps that are described beginning at Set the Network Internet Protocol IP Address on page 7 ATTENTION Do no...

Страница 14: ...e 100 AM at 1890 MHz 10V m with 1 kHz sine wave 80 AM from 2000 2700 MHz EFT B Immunity IEC 61000 4 4 4 kV at 5 kHz on power ports 4 kV at 5 kHz on Ethernet ports Surge Transient Immunity IEC 61000 4...

Страница 15: ...0 Control Systems User Manual publication ENET UM004 Describes how to install configure and operate EtherNet IP Communication Modules in Logix 5000 Control Systems FLEX 5000 Digital I O Modules User M...

Страница 16: ...us serve your documentation needs better If you have any suggestions on how to improve this document complete the How Are We Doing form at http literature rockwellautomation com idc groups literature...

Отзывы: