background image

12

Rockwell Automation Publication 5069-IN019C-EN-P - October 2018

CompactLogix 5480 Controller

7. Insert the wire from an Earth Ground location into the first 

Ground (

)

 

on the RTB. 

The Earth Ground location can be the external SA power 
supply, the DIN rail, or other Earth Ground location.

8. Turn the screwdriver to close the terminal on the wire. 

The screw torque is 0.4 N•m (3.5 lb•in).

This diagram shows an external 240V AC power supply that is 
connected to the SA power RTB when you do not use UPS 
control signals.

Connect Control Signals Via UPS Control RTB

The CompactLogix 5480 controller does not have an internal energy 
storage module that lets the controller save the state of the program if 
system-side power is lost. You must connect an external uninterruptible 
power supply (UPS) to the UPS control RTB to save the state of the 
program if power is lost.

You connect control signals from an external power supply to the UPS 
control RTB to let the controller experience a controlled shutdown 
upon an incoming power loss.

When a UPS connection is detected, the CompactLogix 5480 
controller defaults to initiate shutdown 1 minute after a power 
loss indication.

We recommend that you use 1606 switched mode uninterruptible 
power supplies from Rockwell Automation with a CompactLogix 
5480 controller, for example, the 1606-XLS240-UPS power supply. 

For more information on Bulletin 1606 uninterruptible power 
supplies, see the following:

• Bulletin 1606 DC-UPS Uninterruptible Power Supply 

Installation Instructions, publication 

1606-IN025

• Bulletin 1606 Switched Mode Power Supplies Reference 

Manual, publication 

1606-RM036

The switched mode uninterruptible power supplies use a 12-volt 
battery module to bridge power failures and voltage fluctuations. We 
recommend that you use the 1606-XLSBATASSY1 battery module 
from Rockwell Automation.

You can use other accessories, such as replacement batteries, mounting 
kits, and panel/wall mounting brackets with the battery module. 

For more information on and the battery module and accessories that 
you can use with them, see the following:

• Bulletin 1606 12V 7Ah Battery Modules Installation 

Instructions, publication 

1606-IN011

• Bulletin 1606 Switched Mode Power Supply Battery Modules 

(12V 7Ah) Reference Manual, publication 

1606-RM037

TIP

This symbol 

denotes 

an 

Earth 

Ground 

terminal 

that 

provides 

low 

impedance path between electric circuits and earth for functional 
purposes and provides noise immunity improvement. This connection 
must be made for functional purposes.

24V DC 

Power 

Supply

+

240V AC 

Power 

Supply

+

MOD 

Power

SA AC 

Power

Earth Ground

Содержание 5069-L46ERMW

Страница 1: ...the COS on the controller including One Gigabit Ethernet port as a dedicated OS network interface An integrated DisplayPort for high definition monitor connectivity Two USB 3 0 ports for OS peripheral...

Страница 2: ...o effettuare interventi di manutenzione su di esso leggere il presente documento ed i documenti elencati nella sezione Altre risorse riguardanti l installazione la configurazione ed il funzionamento d...

Страница 3: ...lable Store the equipment in appropriate static safe packaging when not in use ATTENTION In case of malfunction or damage no attempts at repair should be made The controller should be returned to the...

Страница 4: ...ans if necessary 13 Controller status indicators Show the state of the controller in multiple respects 14 Top fan Helps regulate controller temperature Controller ships with fans installed You can rep...

Страница 5: ...de power to the CompactLogix 5480 system IMPORTANT SA power is only required if your application includes local Compact 5000 I O modules that are connected to devices that use SA power For more inform...

Страница 6: ...heat dissipation is 72 W that is the sum of all components in the enclosure In the following equation T 40 and Q 72 In this example the enclosure must have a minimum exterior surface of 0 386 m2 If a...

Страница 7: ...d passed across the MOD power bus ThetotalcontinuouscurrentdrawacrosstheMODpowerbusmustnotbe more than 10 A max at 18 32V DC You must calculate the total MOD power that the controller and all local Co...

Страница 8: ...pactLogix 5480 controllers do not have an embedded power supply that powers the system The system is powered by external power supplies via connections to the various power RTBs on the controller We r...

Страница 9: ...ect an external power source to the MOD power RTB make sure that the MOD power source is properly sized 1 Verify that the external power supply is not powered 2 Strip 12 mm 0 47 in of insulation from...

Страница 10: ...wer source is properly sized For more information o n SA power see SA Power on page 7 1 Confirm that MOD power and SA power sources are turned off 2 Strip 12 mm 0 47 in of insulation from the wires th...

Страница 11: ...not powered on 2 Strip 12 mm 0 47 in of insulation from the wires that you connect to the RTB 3 Insert the wire from the L1 AC connection on the external power supply into the first SA terminal on the...

Страница 12: ...06 switched mode uninterruptible power supplies from Rockwell Automation with a CompactLogix 5480 controller for example the 1606 XLS240 UPS power supply For more information on Bulletin 1606 uninterr...

Страница 13: ...must be greater than 85 charged to be ready The letter R indicates the RTB terminal for this signal Buffering B An input signal from the UPS to the controller that indicates the UPS battery is provid...

Страница 14: ...l on the UPS and a second wire 4 Connect one wire to each terminal on the MOD power RTB a Insert the wire into the terminal b Turn the screwdriver to close the terminal on the wire The screw torque is...

Страница 15: ...wire from the Inhibit 8 connection on the UPS to the Inhibit terminal on the UPS control RTB a Insert the wire into the terminal b Turn the screwdriver to close the terminal on the wire The screw torq...

Страница 16: ...Compact 5000 I O modules see the installation instructions available with each Compact 5000 I O module catalog number InstalltheEndCap You must install an end cap on the right side of the last module...

Страница 17: ...ng tool version 3 02 00 or later RSLinx Classic software version 4 10 00 or later FactoryTalk Linx Enterprise version 6 10 00 or later Logix Designer application version 32 00 00 or later For more inf...

Страница 18: ...ide power that is provided by the controller is removed If SA power that is provided via a 5069 FPD field potential distributor the system does not lose SA power to the right of the field potential di...

Страница 19: ...n project you can use the Minor Faults tab on the Controller Properties dialog box to monitor for these faults Major fault Triggered if both fans fail and the controller goes over the maximum operatin...

Страница 20: ...he fan out of the slot at the top of the controller InstalltheTopReplacementFan 1 Insert the top replacement fan into the slot at the top of the controller Make sure the tabs at the back of the fan ar...

Страница 21: ...fan out of the slot at the bottom of the controller InstalltheBottomReplacementFan 1 Insert the bottom replacement fan into the slot at the bottom of the controller Make sure the tabs at the back of t...

Страница 22: ...ionType USB ports and DisplayPort to MOD Power 300V continuous Double InsulationType USB ports and DisplayPort to SA Power No isolation between Ethernet ports Type tested at 1500V AC for 60 s Wire siz...

Страница 23: ...mpactLogix 5380 Compact GuardLogix 5380 and CompactLogix 5480 Controller Specifications Technical Data publication 5069 TD002 Provides specifications and other technical data for CompactLogix 5380 Com...

Страница 24: ...ments will help us serve your documentation needs better If you have any suggestions on how to improve this document complete the How Are We Doing form at http literature rockwellautomation com idc gr...

Отзывы: