background image

Rockwell Automation Publication 2711PC-UM002F-EN-P - February 2020

19

Install the Terminal

Chapter 2

Product Dimensions

Figure 2

 through 

Figure 4

 provide product dimensions. 

Figure 2 - PanelView Plus 6 Compact - 400 Keypad or Keypad/Touch

Figure 3 - PanelView Plus 6 Compact - 600 Touch

Figure 4 - PanelView Plus 6 Compact - 1000 Touch

Table 14 -  PanelView Plus 6 Compact - 400/600/1000 Product Dimensions

Terminal Size

Input Type

Height (a)

mm (in.)

Width (b)

mm (in.)

Depth (c) 

mm (in.)

400

Keypad or keypad/touch

152 (6.0)

185 (7.28)

60 (2.35)

600

Touch

152 (6.0)

185 (7.28)

68 (2.68)

1000

Touch

248 (9.77)

329 (12.97)

83 (3.27)

6

1

1

6

a

b

c

a

b

c

c

a

b

Содержание 2711PC-B4C20D8

Страница 1: ...PanelView Plus 6 Compact Terminals Catalog Numbers 2711PC K4M20D8 2711PC B4C20D8 2711PC B4C20D8 LR 2711PC T6M20D8 2711PC T6C20D8 2711PC T10C4D8 User Manual OriginalInstructions...

Страница 2: ...its equipment or software described in this manual Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited Throughout this m...

Страница 3: ...es 18 Panel Guidelines 18 Panel Cutout Dimensions 18 Product Dimensions 19 Mount the 400 600 Terminal in a Panel 20 Mount the 1000 Terminal in a Panel 22 Remove and Install the Power Terminal Block 24...

Страница 4: ...y Properties 82 Logo Manager 84 System Information 85 User Accounts 88 Services 89 Network Server Configuration 90 Printer Support 99 PDF Reader 102 Chapter5 InstallandReplaceComponents Required Tools...

Страница 5: ...ade Terminal Firmware over the Network 138 Chapter8 Troubleshooting Status Indicators 141 Terminal Does Not Start Properly 142 Start up Messages and Codes 143 Check Terminal Components 145 Ethernet Co...

Страница 6: ...6 Rockwell Automation Publication 2711PC UM002F EN P February 2020 Table of Contents Notes...

Страница 7: ...oncerning related products from Rockwell Automation You can view or download publications at http www rockwellautomation com literature To order paper copies of technical documentation contact your lo...

Страница 8: ...8 Rockwell Automation Publication 2711PC UM002F EN P February 2020 Preface Notes...

Страница 9: ...h Limited number of displays and alarms in FactoryTalk View Machine Edition ME application and runtime software Primary HMI for CompactLogix controllers Topic Page Software Support 10 PanelView Plus 6...

Страница 10: ...r applications Machine Edition Station is preloaded on each terminal and does not require FactoryTalkView activation 6 10 or later FactoryTalkView Studio for Machine Edition Configuration software for...

Страница 11: ...DC power input non isolated 24V DC nom 18 30V DC 4 Mounting slots four 5 Ethernet port for controller communication 10 100Base T Auto MDI MDI X 6 RS 232 serial port for controller communication printi...

Страница 12: ...ys Use arrow keys for navigation Use Alt arrow to initiate these functions Alt left arrow Home Alt right arrow End Alt up arrow Page Up Alt down arrow Page Down 5 Function keys F1 F8 Keys that can be...

Страница 13: ...rm one of three actions at startup Launch a FactoryTalk View Machine Edition HMI application Launch the FactoryTalk View Machine Edition Configuration mode of the terminal where you load and run appli...

Страница 14: ...6 5 ft Table 7 Power Supply and Power Terminal Blocks Cat No Terminal Model Description Quantity 1606 XLE120E 400 600 and 1000 DIN rail power supply AC to DC 100 240V AC 50 60 Hz 1 2711P 6RSA 400 and...

Страница 15: ...her environments due to conducted or radiated disturbances Korean RadioWave Suitability Registration When so marked this equipment is registered for Electromagnetic Conformity Registration as business...

Страница 16: ...des marquages sur sa plaque d identification quiindiquentlecodedetemp raturepourlesenvironnementsdangereux Lorsque plusieurs produits sont combin s dans un syst me le code de temp rature le plus d fav...

Страница 17: ...es as applicable This associated nonincendive field wiring apparatus has not been evaluated for use in combination with another associated nonincendive field wiring apparatus Nonincendive Field wiring...

Страница 18: ...the panel must be sufficient to hold the terminal and maintain an appropriate seal against water and dust The panel surface must be flat and free of imperfections to maintain an adequate seal and NEMA...

Страница 19: ...t 400 Keypad or Keypad Touch Figure 3 PanelView Plus 6 Compact 600 Touch Figure 4 PanelView Plus 6 Compact 1000 Touch Table 14 PanelView Plus 6 Compact 400 600 1000 Product Dimensions Terminal Size In...

Страница 20: ...imensions on page 18 2 Verify the sealing gasket is present on the terminal This gasket forms a compression type seal Do not use sealing compounds Table 15 Lever Locking Positions Mounting Slot Lever...

Страница 21: ...cated until it is in the final position Follow the appropriate locking sequence for the optimal terminal fit 7 Inspect all levers to verify that they are in the correct and same locked position 6 1 6...

Страница 22: ...ensions on page 18 2 Verify the terminal sealing gasket is properly positioned on the terminal This gasket forms a compression type seal Do not use sealing compounds Be careful not to pinch the legend...

Страница 23: ...surface uniformly 6 Tighten the mounting clips screws to a torque of 0 90 1 1 N m 8 10 lb in by using the specified sequence making sure not to overtighten Mounting Clip Slot Mounting Clip ATTENTION...

Страница 24: ...from the terminal this releases the locking mechanism Follow these steps to install the terminal block 1 Press the terminal block base in first with the block leaning outward WARNING Explosion Hazard...

Страница 25: ...e steps to remove the terminal block from a 1000 terminal 1 Loosen the two screws that secure the terminal block 2 Gently pull the terminal block away from the connector Follow these steps to install...

Страница 26: ...ltage nom Power Consumption max 400 600 Nonisolated 24V DC 18 30V DC 15W 0 6 A at 24V DC 1000 Isolated 24V DC 18 32V DC 70W 2 9 A at 24V DC ATTENTION Do not connect an AC power source to the terminal...

Страница 27: ...connection is required for the following Noise immunity reliability and Electromagnetic Compliance EMC with the European Union EU EMC directive for CE mark conformance Safety by Underwriters Laborator...

Страница 28: ...minals secure the earth ground wire to the functional earth ground terminal on the power terminal block On 1000 terminals secure the earth ground wire to the functional earth screw on the back of the...

Страница 29: ...ration mode and run the configuration options for the terminal default Launch the Windows Explorer desktop You can also configure a terminal to allow desktop access Terminals are initially shipped wit...

Страница 30: ...tem by using the RESET switch 1 Insert a thin nonconductive object into the RESET area 2 Press and release the RESET switch Follow these steps to restart the system from the Windows desktop 1 From the...

Отзывы: