Wiring and Grounding Guidelines for PanelView Plus Terminals    

 5

Remove and Install the 
Power Terminal Block

PanelView Plus terminals are shipped with the power terminal block installed. 
You can remove the terminal block for ease of installation, wiring, and 
maintenance.

PanelView Plus 400 and 600 Terminals

Follow these steps to remove the terminal block in any PanelView Plus 400 and 
600 terminal, including the PanelView Plus Compact 400 and 600 terminals.

1.

Insert the tip of a small screwdriver into the terminal block access slot.

2.

Gently pry the terminal block away from the terminal to release the 
locking mechanism.

Follow these steps to replace the terminal block.

1.

Press the terminal block base in first with the block leaning outward.

2.

Gently push the top of the terminal block back to the vertical position to 
snap in the locking tab.

WARNING: 

Explosion Hazard

Do not disconnect equipment unless power has been switched off and the 
area is known to be nonhazardous. 

Disconnect all power before installing or replacing components. Failure to 
disconnect power may result in electrical shock or damage to the device.

Содержание 2711P

Страница 1: ...Throughout this publication PanelView Plus terminals is used generically to refer to all terminals unless specifically stated Topic Page Important User Information 2 Terms and Definitions 3 Wiring and...

Страница 2: ...nd diagrams No patent liability is assumed by Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual Reproduction of the contents of this ma...

Страница 3: ...ts common connected to earth ground Earth Ground A conducting path between an electric circuit or equipment and ground for safety or EMC reduction In industrial equipment the earth connection is typic...

Страница 4: ...on lines at right angles if they must cross Communication lines can be installed in the same conduit as low level DC I O lines less than 10V Shield and ground cables appropriately to avoid electromagn...

Страница 5: ...mpact 400 and 600 terminals 1 Insert the tip of a small screwdriver into the terminal block access slot 2 Gently pry the terminal block away from the terminal to release the locking mechanism Follow t...

Страница 6: ...teps to install the terminal block 1 Reattach the terminal block to the connector until seated 2 Tighten the two screws that secure the terminal block to the connector Table 1 Power Terminal Block Pow...

Страница 7: ...C5D 2711P K6M20D 2711P T6M20D 2711P B6M20D 2711P K6C20D 2711P T6C20D 2711P B6C20D PanelView Plus 600 2711PC K4M20D 2711PC B4C20D 2711PC T6M20D 2711PC T6C20D 2711PC T10C4D1 PanelView Plus Compact 400 6...

Страница 8: ...ated power supply does not provide galvanic isolation A Class 2 or safety extra low voltage SELV isolated power supply with a 24V DC nominal output voltage is required to power the terminal Figure 1 A...

Страница 9: ...through a star washer then through the ground conductor lug then into the ground bus Use the shortest practical wire length to connect the functional earth ground to a low impedance earth ground The...

Страница 10: ...to 1500 Nonisolated DC Terminals Figure 3 Functional Earth Connection for 400 and 600 DC Terminals Enclosure Wall To Grounding Electrode System Tapped Hole Ground Lug Bolt Star Washer Ground Bus Groun...

Страница 11: ...Hz These are the electrical output ratings of the power supply 24V DC nominal 3 A maximum For more information on this power supply refer to the AC Power Supply Installation Instructions publication...

Страница 12: ...ule with 512 MB nonvolatile memory and RAM 2711P RP8DK Conformal coated logic module with 512 MB nonvolatile memory and RAM 2711P RP9D Logic module with 512 MB nonvolatile memory and RAM 2711P RP9DK C...

Страница 13: ...nce earth ground The ground wire must be either green or green with a yellow stripe Refer to local wiring codes and regulations for grounding requirements Figure 5 Earth Ground Connection for 700 to 1...

Страница 14: ...The power supply converts AC power to DC power provides a SELV output and has electrical input ratings of 85 264V AC 47 63 Hz These are the electrical output ratings of the power supply 24V DC nomina...

Страница 15: ...ange PanelView Plus 400 and 600 PanelView Plus Compact 400 600 24V DC nom 18 30V DC 25 W max 1 0 A at 24V DC PanelView Plus 6 700 to 1500 PanelView Plus 700 to 1500 PanelView Plus Compact 1000 24V DC...

Страница 16: ...Block Series E or Later Logic Modules 3 position Terminal Block Series A D Logic Modules Earth Ground to Ground Bus DC DC DC DC DC DC Functional Earth to Ground Bus PanelView Plus 700 to 1500 or Pane...

Страница 17: ...PanelView Plus 400 2711P K6M5A 2711P T6M5A 2711P B6M5A 2711P K6M20A 2711P B6M20A 2711P K6C5A 2711P T6C5A 2711P B6C5A 2711P K6C20A 2711P T6C20A 2711P B6C20A PanelView Plus 600 Table 10 AC Logic Module...

Страница 18: ...wire length to connect the protective earth ground to a low impedance earth ground The ground wire must be either green or green with a yellow stripe Refer to local wiring codes and regulations for gr...

Страница 19: ...o 1500 AC Terminals IMPORTANT On PanelView Plus 700 to 1500 AC terminals you must connect both protective earth and functional earth to ground ATTENTION The functional earth and protective earth conne...

Страница 20: ...AC Power Ratings Terminal Voltage Range Frequency VA 400 and 600 85 264V AC 47 63 Hz 60VA max 700 to 1500 1 1 Includes PanelView Plus 6 terminals and PanelView Plus terminals supporting FactoryTalk Vi...

Страница 21: ...View ME software version 5 1 or earlier RS 232 Nonisolated Isolated USB Nonisolated Nonisolated Ethernet Isolated Isolated Table 15 400 and 600 Modular Communication Port Isolation Communication Port...

Страница 22: ...RJ45 connector according to IEC 60603 7 The recommended RJ45 connector is available from Sentinel Connector Systems Inc as part number 106S08080058C34 The maximum cable length between the Ethernet po...

Страница 23: ...terminal in a system must be powered by its own power supply with the correct electrical ratings Use a UL Class 2 or an IEC SELV power source to meet regulatory electrical shock and fire prevention r...

Страница 24: ...m returning to the PanelView Plus terminal through earth ground and damaging the terminal Figure 11 Isolated DC to DC Converters to Power Multiple DC Terminals If a system contains multiple PanelView...

Страница 25: ...tructure Current flowing through earth ground can damage the terminal Connect the Power Wires Correctly Make sure you connect the DC and DC wires to the correct positions on the power terminal block T...

Страница 26: ...solated PanelView Plus terminal is not connected to earth ground internally within the product The PanelView Plus 700 to 1500 isolated DC terminals do not require a separate power source for each term...

Страница 27: ...and chassis If another device by using the same power source has a DC common to the earth ground connection then two parallel current paths exist One path leads from the DC of the PanelView Plus term...

Страница 28: ...lated DC PanelView Plus Terminals The power supply of the isolated DC PanelView Plus 700 to 1500 terminals lets you power multiple terminals from one DC power source without creating a ground loop DC...

Страница 29: ...ground structure has a lower impedance than the common wiring the motor current will flow through earth ground and the PanelView Plus terminal The motor current could damage the terminal Nonisolated D...

Страница 30: ...lated DC PanelView Plus Terminals The isolated DC PanelView Plus terminals can be used in a system with other DC equipment powered by a single DC power source Single Power Supply with Isolated DC Term...

Страница 31: ...minal s earth ground If the communication device is remote from the PanelView Plus terminal and has nonisolated ports both devices are referenced as close as their earth grounds are referenced Events...

Страница 32: ...ation equipment power supply and do not present a problem with the communication equipment alone However when the communication equipment is connected to the PanelView Plus terminal the 24V DC power s...

Страница 33: ...ves information on how to install operate configure and troubleshoot these devices PanelView Plus Terminals User Manual publication 2711P UM001 Provides an overview of the PanelView Plus and PanelView...

Страница 34: ......

Страница 35: ......

Страница 36: ...m within the first 24 hours of installation review the information that is contained in this manual You can contact Customer Support for initial help in getting your product up and running New Product...