High-bright Display Modules
Mounting Clearances
Allow adequate clearance around the terminal, inside the enclosure, for adequate ventilation.
Consider heat produced by other devices in the enclosure. The ambient temperature around the
terminals must be between 0…55 °C (32…131 °F).
These minimum clearances are required for ventilation:
• Top clearance: 51 mm (2 in.)
• Bottom clearance: 102 mm (4 in.)
• Side clearances: 25 mm (1 in.)
• Back clearance: 25 mm (1 in.)
Minimum side clearance for insertion of memory card is 102 mm (4 in.).
Panel Cutout Dimensions
Use the full size template shipped with your terminal to mark the cutout dimensions.
The 1250 Touch PanelView Plus, PanelView Plus CE, and PanelView Plus 6 Terminals are 257
mm (10.11 in.) high and 338 mm (13.29 in.) wide.
Mount the Terminal in a Panel
Four mounting clips secure the terminal to the panel.
Follow these steps to mount the terminal in a panel.
1. Cut an opening in the panel by using the panel cutout shipped with the terminal.
ATTENTION:
Disconnect all electrical power from the panel before making the panel cutout.
Make sure the area around the panel cutout is clear.
Take precautions so metal cuttings do not enter any components already installed in the panel.
Failure to follow these instructions may result in personal injury or damage to panel components.